36 - 140
Fault Tracking
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P01.06
ACC time of
the starting
step of S curve
0.0~50.0s
0.1s
◎
P01.07
DEC time of
the ending step
of S curve
0.1s
◎
P01.08
Stop mode
selection
0: Decelerate to stop
. After the stop command becomes
valid, the inverter decelerates to reduce the output frequency
during the set time. When the frequency decreases to 0Hz,
the inverter stops.
1: Coast to stop
. After the stop command becomes valid,
the inverter ceases the output immediately. And the load
coasts to stop at the mechanical inertia.
0
○
P01.09
Starting
frequency of
DC braking
Starting frequency of DC braking
: start the DC braking
when running frequency reaches starting frequency
determined by P1.09.
Waiting time before DC braking
: Inverters blocks the
output before starting the DC braking. After this waiting time,
the DC braking will be started so as to prevent over-current
fault caused by DC braking at high speed.
DC braking current
: the value of P01.11 is the percentage
of rated current of inverter. The bigger the DC braking
current is, the greater the braking torque is.
DC braking time
: the retention time of DC braking. If the
time is 0, the DC braking is invalid. The inverter will stop at
the set deceleration time.
0.00Hz
○
P01.10
Waiting time
before DC
braking
0.00s
○
P01.11
DC braking
current
0.0%
○
P01.12
DC braking
time
0.00s
○