Programming and Parameters
3-31
PowerFlex 700S Phase II AC Drive User Manual -
Publication 20D-UM006G-EN-P – July 2008
190
PI Integ Output
Displays the output value of the integral channel of the Process Control regulator. A value of
1 can represent either base motor speed, motor rated torque, or 100% for some external
function.
Units:
Default:
Min/Max:
P.U.
0.0000
-/+8.0000 pu
RO Real
191
PI High Limit
The high limit of the Process Control regulator output. A value of 1 can represent either base
motor speed, motor rated torque, or 100% for some external function.
Units:
Default:
Min/Max:
P.U.
0.1000
0.0000/8.0000
✓
RW Real
192
PI Lower Limit
The low limit of the Process Control regulator output. A value of 1 can represent either base
motor speed, motor rated torque, or 100% for some external function.
Units:
Default:
Min/Max:
P.U.
-0.1000
-8.0000/0.0000
✓
RW Real
196
ParamAccessLevel
The value of this parameter establishes the level of parameter access for the Human Interface
Module (HIM).
•
Value 0 - Basic grants access to the minimum number of parameters
•
Value 1 - Advanced grants access to a larger group of parameters
Default:
Options:
0 =
0 =
1 =
“Basic”
“Basic”
“Advanced”
RW 16-bit
Integer
201
Language
Selects the display language when using an LCD HIM. Currently, only option 0 - “English” is
available.
Default:
Options:
0 =
0 =
1 =
“English”
“English”
“Alt Language”
RW 16-bit
Integer
202
Time Axis Rate
Sets rate (1/sec) for the Time Function Generator to ramp from an output of 0 to 1 and from 1
to 0.
Units:
Default:
Min/Max:
/Sec
1.0000
0.0100/20.0000
✓
RW Real
203
Time Axis Output
The output of the Time Function Generator. When the Time Function Generator is enabled by
[Logic Command] bit 3 “Time Axis En”, or
[Control Options], bit 24 “Time Axis
En”, the value of this parameter ramps from 0 to 1 at a rate determined by
[Time Axis
Rate]. Conversely, when the Time Function Generator is disabled, the value of this parameter
ramps from 1 to 0.
Default:
Min/Max:
0.0000
0.0000/1.0000
RO Real
204
LimGen Y axis Mx
Sets
[Limit Gen Hi Out] and
[Limit Gen Lo Out] when the absolute value of
[LimGen X axis In] is greater than or equal to 1.
Units:
Default:
Min/Max:
P.U.
0.2500
0.0000/8.0000
✓
RW Real
205
LimGen Y axis Mn
Sets
[Limit Gen Hi Out] and
[Limit Gen Lo Out] when the absolute value of
[LimGen X axis In] is equal to 0.
Units:
Default:
Min/Max:
P.U.
0.0500
0.0000/8.0000
✓
RW Real
206
LimGen X axis In
The X axis input to the Limit Generator. Typically this parameter is linked to a speed reference
or to
[Time Axis Output].
Default:
Min/Max:
0.0000
-/+8.0000 pu
✓
RW Real
207
Limit Gen Hi Out
Displays the positive output of the Limit Generator. When
greater than or equal to 1, this value equals
[Limit Gen Y axis Mx]. When Par 206
[Limit Gen X axis In] is equal to 0, this value equals
[Limit Gen Y axis Mn]. For values
of X Axis input between 0 and 1, the value of this parameter is interpolated from Y axis min.
and max. values. Typically it is linked to
[PI Integ HLim].
Units:
Default:
Min/Max:
P.U.
8.0000
0.0000/8.0000
RO Real
208
Limit Gen Lo Out
Displays the negative output of the Limit Generator. The value of this parameter is the
negative of
[Limit Gen Hi Out]. Typically it is linked to
[PI Integ LLim].
Units:
Default:
Min/Max:
P.U.
-8.0000
-8.0000/0.0000
RO Real
210
PeakDtct Ctrl In
Sets the configuration of the two peak/level detectors. Peak detection (when “set” and “hold” are off) causes the output to capture the peak min./max.
•
Bit 2 “Peak1SelHigh” and bit 6 “Peak2SelHigh” determine if the peak/level detector is positive or negative. If the bit is set the detector detects positive peaks or
levels above the preset. If the bit is not set the detector detects "valleys" or levels below the preset. The output shows the min. or max. peak.
•
Bit 0 “Peak 1 Set” bit is used to reset the output to the value in
[PeakDtct1 Preset] (default 0). Bit 4 “Peak 2 Set” bit is used to reset the output to the
value in
[PeakDtct2 Preset] (default 0).
•
Bit 1“Peak 1 Hold” is used to hold the output at the present value in Par 214 [PeakDtct1 Preset]. Bit 5 “Peak 2 Hold” is used to hold the output at the present
value in Par 218 [PeakDtct2 Preset].
No.
Name
Description
Values
Linkab
le
R
ead-Wr
ite
Da
ta
T
ype
Options
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
P
eak
2SelHigh
P
eak
2
Hold
P
eak
2
Set
Re
se
rv
ed
P
eak
1SelHigh
P
eak
1
Hold
P
eak
1
Set
Default
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Bit
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
0 = False
1 = True
Содержание PowerFlex 700S
Страница 1: ...USER MANUAL Firmware Versions 1 xxx 4 002 PowerFlex 700S High Performance AC Drive Phase II Control ...
Страница 58: ...2 8 Start Up PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 Notes ...
Страница 147: ...Programming and Parameters 3 89 PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 ...
Страница 278: ...D 8 HIM Overview PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 Notes ...
Страница 316: ...Index 6 PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 ...
Страница 317: ......