Programming and Parameters
3-61
PowerFlex 700S Phase II AC Drive User Manual -
Publication 20D-UM006G-EN-P – July 2008
No.
Name
Description
Values
Linka
b
le
Read-Write
Data T
ype
401 Rated
Volts
Nameplate voltage rating of the inverter. The drive automatically sets this at power up.
Units:
Default:
Min/Max:
Volt
480
75/750
RO 16-bit
Integer
402 PWM
Frequency
Carrier frequency for the PWM output of the drive. Drive derating may occur at higher
carrier frequencies. For derating information, refer to the PowerFlex Reference Manual.
Default is dependant on power structure of the drive.
Note: This parameter was changed for firmware version 3.04 to not allow changes while
the drive is running.
Units:
Default:
Min/Max:
kHz
2.0000 (Fr 5, 6, 9)
4.0000 (Fr 1-4)
1.0000/15.0000 (10.0000 Fr 5, 6, 9)
RW Real
403 Voltage
Class
Sets the drive configuration for high or low voltage class (I.e. a 400 or 480V ac drive).
Allows choice of configuration and affects many drive parameters including drive rated
current, voltage, power, over loads and maximum PWM carrier frequency.
Note: This parameter was changed for firmware version 3.04 to allow the
drive to produce an output voltage limited by
[Maximum
Voltage] (or maximum voltage defined by the DC bus voltage level,
[DC Bus Voltage], and DC bus voltage utilization limit,
[Bus Util Limit]).
Default:
Options:
3 =
2 =
3 =
“High Voltage”
“Low Voltage”
“High Voltage”
404 Dead
Time
The time delay between turning off and turning on an upper device and a lower device in
the power structure. This parameter is set at power up and is not user adjustable.
Units:
Default:
Min/Max:
μ
Sec
5.0000
2.0000/100.0000
RO Real
405
Dead Time Comp
The amount of voltage correction used to compensate for the loss of voltage during dead
time. Do not adjust. Contact factory for alternative settings.
Units:
Default:
Min/Max:
%
0
0/200
RW 16-bit
Integer
406
Power Loss Mode
Enter a value to configure the drive's response to a loss of input power, as sensed by an
input voltage below the value specified in
[Power Loss Level].
•
Enter a value of “0” to make the drive fault and coast to a stop (supply no current to the
motor) after the amount of time specified in
[Power Loss Time] has expired.
•
Enter a value of “2” to make the drive fault and continue "normal" operation after the
amount of time specified in Par 407 [Power Loss Time] has expired.
•
Enter a value of “5” to make the drive provide only motor flux current during the power
loss time.
Default:
Options:
0 =
0 =
1 =
2 =
“Coast”
“Coast”
3 = “Reserved”
“Reserved”
4 = “Reserved”
“Continue”
5 = “Flux Only”
407
Power Loss Time
Sets the amount of time that the drive will remain in a ride through condition before a fault
is detected.
Units:
Default:
Min/Max:
Sec
2.0000
0.0000/60.0000
RW Real
408
Power Loss Level
Sets the percentage of the bus voltage at which ride-through begins and modulation
ends. When the bus voltage falls below this level and
[Power Loss Mode] is set to
0 “Coast” or 5 “Flux Only”, an alarm (F92 “Ride Thru”) will be displayed on the HIM and
the drive prepares for an automatic restart. Enter a percentage of the bus voltage derived
from the high voltage setting for the voltage class. For example: On a 400-480V drive,
Note: The definition was updated to include the bit settings for parameter 406 for firmware
version 4.002.
Units:
Default:
Min/Max:
Scale:
%
22.1
15/95
0
RW 16-bit
Integer
409 Line
Undervolts
Controls the level of bus voltage that is needed to complete precharge and sets the level
for undervoltage alarm/fault detection. Enter a percentage of the bus voltage derived from
the value in
[Rated Volts].
For example: on a 480V drive,
Units:
Default:
Min/Max:
%
61.5000
10.0000/90.0000
RW Real
410 PreChrg
TimeOut
Sets the time duration of precharge. If bus voltage does not stabilize within this amount of
time, a Precharge Error exception event occurs.
Units:
Default:
Min/Max:
Sec
30.0000
10.0000/180.0000
RW Real
411 PreChrg
Control
Must equal 1 to allow drive to exit precharge and begin to run. Link this parameter to a
controller output word to coordinate the precharge of multiple drives.
Default:
Options:
1 =
0 =
1 =
“Enbl PrChrg”
“Hold PrChrg”
“Enbl PrChrg”
0.221
480Vac
2
×
×
150Vdc
=
0.615
480Vac
2
×
×
418Vdc
=
Содержание PowerFlex 700S
Страница 1: ...USER MANUAL Firmware Versions 1 xxx 4 002 PowerFlex 700S High Performance AC Drive Phase II Control ...
Страница 58: ...2 8 Start Up PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 Notes ...
Страница 147: ...Programming and Parameters 3 89 PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 ...
Страница 278: ...D 8 HIM Overview PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 Notes ...
Страница 316: ...Index 6 PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 ...
Страница 317: ......