3-54
Programming and Parameters
PowerFlex 700S Phase II AC Drive User Manual -
Publication 20D-UM006G-EN-P – July 2008
357
Curr Ref TP Sel
Enter or write a value to select current reference data displayed in
[Curr Ref TP Data].
Note: Added values 20 - 52 for firmware version 3.03. Added value 53 for firmware version
4.001.
Default:
Options:
0 =
0 =
1 =
2 =
3 =
4 =
5 =
6 =
7 =
8 =
9 =
10 =
11 =
12 =
13 =
14 =
15 =
16 =
17 =
18 =
19 =
20 =
21 =
22 =
23 =
24 =
25 =
26 =
“Zero”
“Zero”
27 = “Rated Vds”
“Iq Sum”
28 = “Rated Vqs”
“Iq Lim In”
29 = “RatedLamdVds”
“Iq Lim Out”
30 = “RatedLamdIds”
“Iq Rate Stat”
31 = “RatedLamd ds”
“IqLmOutNoFil”
32 = “RatedLamd qs”
“MtrCrLimStat”
33 = “Iqs”
“Lim'dMtrCrLm”
34 = “Ids”
“Iq Act Limit”
35 = “Vqs”
“Iq Cal Gain”
36 = “Vds”
“Min Lim Stat”
37 = “We”
“Iq Prescale”
38 = “Torque”
“IqtoIs Stat”
39 = “Torque Filtr”
‘Flux Status”
40 = “Lamda Ids”
“Flux LPF Out”
41 = “Lamda Iqs”
“Is Per Unit”
42 = “Lamda Vds”
“Iq Actl +Lim”
43 = “Lamda Vqs”
“Iq Actl -Lim”
44 = “Lamda ds”
“Flx Filt Hld”
45 = “Lamda qs”
“Inverse Flux”
46 = “Lamda ds Flt”
“Impedance PU”
47 = “Lamda qs Flt”
“ImpedanceOhm”
48 = “Torque Ref”
“Rated We”
49 = “Iq Reference”
“Leak Induct”
50 = “1/Motor Pole”
“Rated Torque”
51 = “1/Rated Iqs”
“Rated Ids”
52 = “1/Rated Torq”
“Rated Iqs”
53 = “Rs Temp Coef”
358
Curr Ref TP Data
Sets the limit value for the motor torque producing current.
Units:
Default:
Min/Max:
P.U.
0.0000
-/+8.0000 pu
RO Real
359
Motor Flux Est
The Q-axis motor voltage is divided by the motor frequency while field weakening is active.
This value is used to convert the torque command to a motor current (Iqs) command.
Units:
Default:
Min/Max:
P.U.
0.0000
-/+8.0000 pu
RO Real
360
Min Flux
Sets the smallest level of flux used to convert
[Motor Torque Ref] to a current
reference above base speed. Note: Changed the minimum value from “0.2500” to “0.1000” for
firmware version 4.001.
Units:
Default:
Min/Max:
P.U.
0.2500
0.1000/1.0000
✓
RW Real
361
Flx LpassFilt BW
Sets the bandwidth of the low pass filter that adjusts the response of the flux estimate used in
the torque to current conversion. Since the field time constant varies between motors, a better
control response may be obtained by adjusting the filter time constant. Normally this
parameter is not changed unless a significant disturbance occurs as the motor enters field
weakening AND
[Min Flux] is less than 1 per unit.
Units:
Default:
Min/Max:
R/S
12.0000
0.5000/100.0000
✓
RW Real
362
Current Limit Gain
Sets the responsiveness of the current limit. This parameter should not be changed by the
user.
Note: This parameter was added for firmware version 2.03.
Default:
Min/Max:
250
0/10000
RW 16-bit
Integer
363
Ki Current Limit
Current Limit Integral gain. This gain is applied to the current limit error signal to eliminate
steady state current limit error. A larger value increases overshoot during a step of motor
current/load. This parameter should not be changed by the user.
Note: This parameter was added for firmware version 2.03.
Default:
Min/Max:
1500
0/10000
RW 16-bit
Integer
364
Kd Current Limit
Current Limit Derivative gain. This gain is applied to the sensed motor current to anticipate a
current limit condition. A larger value reduces overshoot of the current relative to the current
limit value. This parameter should not be changed by the user.
Note: This parameter was added for firmware version 2.03.
Default:
Min/Max:
500
0/10000
RW 16-bit
Integer
365
366
367
Fdbk LsCnfg Pri
Fdbk LsCnfg Alt
Fdbk LsCnfgPosit
Enter a value to configure the drive's response to an Encoder 0/1 Loss exception event.
•
0 - Ignore configures the drive to continue running, as normal, when this event occurs.
•
1 - Alarm configures the drive to continue running and set the appropriate alarm bit when
this event occurs.
•
2 - FltCoastStop configures the drive to perform a coast stop and set the appropriate fault
bit, in response to this event.
Default:
Default:
Default:
Options:
2 =
1 =
1 =
1 =
2 =
“FltCoastStop”
“Alarm”
“Alarm”
“Alarm”
“FltCoastStop”
368
Cnv NotLogin Cfg
Configures the 700L drive’s response when the active convertor is not logged-in via a DPI
port.
Note: This parameter was added for firmware version 3.01.
Default:
Options:
2 =
0 =
1 =
2 =
“FltCoastStop”
“Ignore””
“Alarm”
“FltCoastStop”
No.
Name
Description
Values
Linkab
le
R
ead-Wr
ite
Da
ta
T
ype
Содержание PowerFlex 700S
Страница 1: ...USER MANUAL Firmware Versions 1 xxx 4 002 PowerFlex 700S High Performance AC Drive Phase II Control ...
Страница 58: ...2 8 Start Up PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 Notes ...
Страница 147: ...Programming and Parameters 3 89 PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 ...
Страница 278: ...D 8 HIM Overview PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 Notes ...
Страница 316: ...Index 6 PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 ...
Страница 317: ......