Programming and Parameters
3-63
PowerFlex 700S Phase II AC Drive User Manual -
Publication 20D-UM006G-EN-P – July 2008
416 Brake
PulseWatts
Limits the power delivered to the external Dynamic Brake (DB) resistor for one second,
without exceeding the rated element temperature. You may change the value of this
parameter only if you have selected an external DB resistor (set bit 1 “Brake Extern” of
[Brake/Bus Cnfg]. If this rating is not available from the resistor vendor, you can
approximate it with this equation:
[Brake PulseWatts] = 75,000 x Weight, where
Weight equals the weight of resistor wire element in pounds (not the entire weight of the
resistor). Another equation you can use is: Par 416 [Brake PulseWatts] = Time Constant x
Brake Watts; where Time Constant equals the amount of time to reach 63% of its rated
temperature while the maximum power is applied, and Brake Watts is the peak power
rating of the resistor.
Note: The maximum value was changed from 1000000.0000 to 1000000000.0000 for
firmware version 3.01.
Units:
Default:
Min/Max:
Watt
2000.0000
1.0000/1000000000.0000
RW Real
417 Brake
Watts
Sets the continuous rated power reference for the Dynamic Brake (DB). You may change
the value of this parameter only if you have selected and external DB resistor (set bit 1
“Brake Extern” of
[Brake/Bus Cnfg].
Note: The maximum value was changed from 5000.0000 to 500000.0000 for firmware
version 3.01.
Units:
Default:
Min/Max:
Watt
100.0000
0.0000/500000.0000
RW Real
418
Brake TP Sel
Enter or write a value to select the drive brake data displayed in
[Brake TP Data].
Default:
Options:
0 =
0 =
1 =
2 =
3 =
4 =
5 =
6 =
7 =
8 =
9 =
“Zero”
“Zero”
10 = “Data State”
“Duty Cycle”
11 = “MC BrakeEnbl”
“Power Actual”
12 = “1/rdb”
“Max BodyTemp”
13 = “1/th_eb”
“Max ElemTemp”
14 = “1/ce”
“BodyTemp Act”
15 = “tamax”
“ElemTemp Act”
16 = “1/th_ba”
“BTmpTripStat”
17 = “1/cb”
“ETmpTripStat”
18 = “DB IGBT Amp”
“Int DB Ohms”
419
Brake TP Data
[Brake TP Sel].
Default:
Min/Max:
0.0000
-/+2200000000.0000
RO Real
420
Pwr Strct Mode
Displays the power structure used in the drive. This is an identifier to the firmware for power structure control.
Bit 0 “Lo Pwr Strct” = PowerFlex 700S Frame 1 to 6
Bit 1 “Hi Pwr Strct” = PowerFlex 700S above Frame 6
Bit 3 “Parallel Drv” = PowerFlex 700S Frame 12
Note: Bit 3 “Parallel Drv” was added for firmware version 3.01.
421
Iqs Integ Freq
Sets the break frequency of the torque producing (q-axis) current regulator. This and
[Iqs Reg P Gain] determine the integral gain for the q-axis current regulator. Set by
the autotune procedure. Do not change this value.
Units:
Default:
Min/Max:
R/S
10
0/32767
RW 16-bit
Integer
422
Iqs Reg P Gain
Sets the proportional gain of the torque producing (q-axis) current regulator. Set by the
autotune procedure. Do not change this value.
Default:
Min/Max:
Scale:
1.0
0.0/100.0
x 10
RW 16-bit
Integer
423
Iqs Rate Limit
Sets the limit of the rate of change for the torque producing (q-axis) current regulator. Do
not change this parameter. Use
[Iq Rate Limited] to control the q-axis current rate
limit.
Units:
Default:
Min/Max:
Scale:
%/mS
800.0
0.0/800.0
x 10
RW 16-bit
Integer
424
Flux Ratio Ref
Active only in the Field Oriented Control (FOC) 2 motor control mode (when
[Motor Ctrl Mode] equals 1 - “FOC 2”). Provides a scaling factor for the flux producing
(d-axis) current reference.
•
When active (
[FVC2 Mode Config], bit 28 “FlxRatRef Use” is set), Flux
Producing (d-axis) Current Reference =
[Flux Current] x Par 424 [Flux Ratio
Ref].
•
When inactive (Par 511 [FVC2 Mode Config], bit 28 “FlxRatRef Use” is cleared) Flux
Producing (d-axis) Current Reference = Par 488 [Flux Current] below base speed and
Flux Producing (d-axis) Current Reference = Par 488 [Flux Current] x motor base
speed/motor speed above base speed.
Units:
Default:
Min/Max:
Scale:
%
99.99
12.50/399.99
100 = 32767
RW 16-bit
Integer
425 Flux
Rate
Limit
Sets the limit for the maximum rate of change for flux producing (d-axis) current.
Units:
Default:
Min/Max:
Scale:
%/mS
1.0
0.0/195.3
x 10
RW 16-bit
Integer
No.
Name
Description
Values
Linkab
le
R
ead-Wr
ite
Da
ta
T
ype
Options
Re
ser
ve
d
Re
ser
ve
d
Re
ser
ve
d
Re
ser
ve
d
Re
ser
ve
d
Re
ser
ve
d
Re
ser
ve
d
Re
ser
ve
d
Re
ser
ve
d
Re
ser
ve
d
Re
ser
ve
d
Re
ser
ve
d
P
aral
le
l Dr
v
PF
70
0L
Hi Pwr
Strc
t
Lo
Pw
rSt
rc
t
Default
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Bit
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
0 = False
1 = True
Содержание PowerFlex 700S
Страница 1: ...USER MANUAL Firmware Versions 1 xxx 4 002 PowerFlex 700S High Performance AC Drive Phase II Control ...
Страница 58: ...2 8 Start Up PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 Notes ...
Страница 147: ...Programming and Parameters 3 89 PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 ...
Страница 278: ...D 8 HIM Overview PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 Notes ...
Страница 316: ...Index 6 PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 ...
Страница 317: ......