3-64
Programming and Parameters
PowerFlex 700S Phase II AC Drive User Manual -
Publication 20D-UM006G-EN-P – July 2008
426
Flux Satur Coef
This represents the amount of flux current required to compensate for the flux saturation
effect of the motor. Active only for FOC 2 motor control mode.
Units:
Default:
Min/Max:
Scale:
%/
0.0
0.0/51.3
x 10
RW 16-bit
Integer
427
PM Mtr CEMF Comp
Provides CEMF compensation for the torque producing (q-axis) current in the permanent
magnet motor mode.
Units:
Default:
Min/Max:
%
0
0/100
RW 16-bit
Integer
428
IReg IGain Fctr
Adjustment for current regulator integral frequency factor (gain).
Default:
Min/Max:
1
1/20
RW 16-bit
Integer
429
Ids Integ Freq
Sets the break frequency of the flux producing (d-axis) current regulator. This and
[Ids Reg P Gain] determine the integral gain for the d-axis current regulator. Set by the
autotune procedure. Do not change this value.
Units:
Default:
Min/Max:
R/S
10
0/32767
RW 16-bit
Integer
430
Ids Reg P Gain
Sets the proportional gain of the flux producing (d-axis) current regulator. Set by the
autotune procedure. Do not change this value.
Default:
Min/Max:
Scale:
1.0
0.0/100.0
x 10
RW 16-bit
Integer
431
Test Current Ref
Sets the current reference used for Motor Control (MC) Test Mode.
Units:
Default:
Min/Max:
Scale:
%
50.0
0.0/799.9
x 10
RW 16-bit
Integer
432
Test Freq Ref
Sets the frequency reference used for Motor Control (MC) Test Mode.
Note: The default value was changed for firmware version 2.03.
Units:
Default:
Min/Max:
Scale:
%
1.0
-/+799.9
x 10
RW 16-bit
Integer
433
Test Freq Rate
Sets the rate of change of frequency reference used for Motor Control (MC) Test Mode.
Units:
Default:
Min/Max:
Scale:
% /S
5.0
0.0/1000.0
x 10
RW 16-bit
Integer
434 Mtr
Vds
Base
Displays the motor flux producing (d-axis) voltage command when running at nameplate
motor speed and load. This value is determined during the auto-tune procedure. Do not
change this value. Used only in FOC modes.
Default:
Min/Max
0
-8192/0
RO 16-bit
Integer
435 Mtr
Vqs
Base
Displays the motor torque producing (q-axis) voltage command when running at
nameplate motor speed and load. This value is determined during the auto-tune
procedure. Do not change this value. Used only in FOC modes.
Default:
Min/Max:
0
0/8192
RO 16-bit
Integer
437 Vqs
Max
Displays the maximum torque producing (q-axis) voltage allowed on the motor.
Adaptation is disabled below this voltage. This value is determined during the auto-tune
procedure. Do not change this value. Used only in FOC modes.
Default:
Min/Max:
7971
0/32767
RW 16-bit
Integer
438 Vds
Max
Displays the maximum flux producing (d-axis) voltage allowed on the motor. Adaptation is
disabled below this voltage. This value is determined during the auto-tune procedure. Do
not change this value. Used only in FOC modes.
Default:
Min/Max:
5793
0/32767
RW 16-bit
Integer
439 Vqs
Min
Displays the minimum torque producing (q-axis) voltage required for motor control
adaptation. This value is determined during the auto-tune procedure. Do not change this
value. Used only in FOC modes.
Default:
Min/Max:
246
-/+32767
RW 16-bit
Integer
440 Vds
Min
Displays the minimum flux producing (d-axis) voltage required for motor control
adaptation. Adaptation is disabled below this voltage. This value is determined during the
auto-tune procedure. Do not change this value.
Default:
Min/Max:
246
-/+32767
RW 16-bit
Integer
441 Vds
Fdbk
Filt
Displays measured filtered motor flux producing (d-axis) voltage.
Default:
Min/Max:
0
-/+32767
RO 16-bit
Integer
442 Vqs
Fdbk
Filt
Displays measured filtered motor torque producing (q-axis) voltage.
Default:
Min/Max:
0
-/+32767
RO 16-bit
Integer
443
Flux Reg P Gain1
Sets the Proportional (P) gain for the flux regulator. Do not change this value.
Default:
Min/Max:
150
0/32767
RW 16-bit
Integer
444
Flux Reg I Gain
Sets the Integral (I) gain for the flux regulator. Do not change this value.
Default:
Min/Max:
350
0/32767
RW 16-bit
Integer
445
Slip Gain Max
Displays the maximum slip frequency allowed in the motor control. The scaling is in hertz
x 256. This value is determined during the auto-tune procedure. Do not change this value.
Units:
Default:
Min/Max:
%
300
100/10000
RW 16-bit
Integer
446
Slip Gain Min
Displays the minimum slip frequency allowed in the motor control. The scaling is in hertz x
256. This value is determined during the auto-tune procedure. Do not change this value.
Units:
Default:
Min/Max:
%
50
0/100
RW 16-bit
Integer
No.
Name
Description
Values
Linkab
le
R
ead-Wr
ite
Da
ta
T
ype
Содержание PowerFlex 700S
Страница 1: ...USER MANUAL Firmware Versions 1 xxx 4 002 PowerFlex 700S High Performance AC Drive Phase II Control ...
Страница 58: ...2 8 Start Up PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 Notes ...
Страница 147: ...Programming and Parameters 3 89 PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 ...
Страница 278: ...D 8 HIM Overview PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 Notes ...
Страница 316: ...Index 6 PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 ...
Страница 317: ......