Programming and Parameters
3-109
PowerFlex 700S Phase II AC Drive User Manual -
Publication 20D-UM006G-EN-P – July 2008
1058
MulDiv 2 Mul
Set this value as the multiplier to the value of
[MulDiv 2 Input]. The result will be
divided by
. See Par 1057.
Default:
Min/Max:
0.0000
-/+2200000000.0000
✓
RW Real
1059
MulDiv 2 Div
Set this value as the divisor of the result of
. The result will be loaded into
. See Par 1057.
Default:
Min/Max:
0.0000
-/+2200000000.0000
✓
RW Real
1060
MulDiv 2 Result
This is the result output from the Multiplication and Division function. See
Default:
Min/Max:
0.0000
-/+2200000000.0000
RO Real
1061
Logic Config
Set this parameter to configure the logic routine in Pars
-
. The result of this logic routine is displayed in
[Logic/Cmpr State]. There are three
configurable logic blocks as displayed below. Each block can be configured as (AND / NAND / OR / NOR / XOR / NXOR). Select the functions as desired. Multiple
operation selection for one block will result in the first selection (least significant bit) being the active mode.
1062
Logic/Cmpr State
Displays the logical states of the Logic routine (Pars
) and the results of the compare functions (Par
).
1063
Logic 1A Data
Selects the data word for the first input to Logic Block 1. See
[Logic Config].
Default:
Min/Max:
0
32 bits of data
✓
RW 32-bit
Boolean
1064
Logic 1A Bit
[Logic 1A Data] for the first input to Logic Block 1.
Note: To invert the selected input enter the desired bit as negative. Use -32 to invert bit 0.
Default:
Min/Max:
0
-31/32
RW 16-bit
Integer
1065
Logic 1B Data
Selects the data word for the second input to Logic Block 1. See
[Logic Config].
Default:
Min/Max:
0
32 bits of data
✓
RW 32-bit
Boolean
1066
Logic 1B Bit
[Logic 1B Data] for the second input to Logic Block 1.
Note: To invert the selected input enter the desired bit as negative. Use -32 to invert bit 0.
Default:
Min/Max:
0
-31/32
RW 16-bit
Integer
1067
Logic 2A Data
Selects the data word for the first input to Logic Block 2. See
[Logic Config]
Default:
Min/Max:
0
32 bits of data
✓
RW 32-bit
Boolean
1068
Logic 2A Bit
[Logic 2A Data] for the first input to Logic Block 2.
Note: To invert the selected input enter the desired bit as negative. Use -32 to invert bit 0.
Default:
Min/Max:
0
-31/32
RW 16-bit
Integer
1069
Logic 2B Data
Selects the data word for the second input to Logic Block 2. See
[Logic Config].
Default:
Min/Max:
0
32 bits of data
✓
RW 32-bit
Boolean
No.
Name
Description
Values
Linkab
le
R
ead-Wr
ite
Da
ta
T
ype
And,
Nand,
Or, Nor,
Xor,
Nxor
And,
Nand,
Or, Nor,
Xor,
Nxor
And,
Nand,
Or, Nor,
Xor,
Nxor
1062
00
1062
02
1062
01
1063
1065
1067
1069
Logic 1A Data
Logic 1B Data
Logic 2A Data
Logic 2B Data
1064
1066
1068
1070
Logic 1A Bit
Logic 1B Bit
Logic 2A Bit
Logic 2B Bit
Logic /Cmpr State
(Logic 1 Result)
(Logic 3 Result)
(Logic 2 Result)
1061
xx
Logic Config
Options
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Logic 3 NXOR
Logic 3 XOR
Logic 3 NOR
Logic 3 OR
Logic 3 NAND
Logic 3 AND
Logic 2 NXOR
Logic 2 XOR
Logic 2 NOR
Logic 2 OR
Logic 2 NAND
Logic 2 AND
Logic 1 NXOR
Logic 1 XOR
Logic 1 NOR
Logic 1 OR
Logic 1 NAND
Logic 1 AND
Default
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Bit
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
0 = False
1 = True
<
=
>
=
1071
1072
1062
04
1062
05
<
=
>
=
1073
1074
1062
06
1062
07
Compare 1A
Compare 1B
Compare 2A
Compare 2B
(Cmpr 1 A>/=B)
(Cmpr 2 A</=B)
(Cmpr 2 A>/=B)
(Cmpr 1 A</=B)
Logic /Cmpr State
Logic /Cmpr State
Options
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Cm
pr
2
A>/=B
Cm
pr
2
A</=B
Cm
pr
1
A>/=B
Cm
pr
1
A</=B
Re
se
rv
ed
Logic 3 Rslt
Logic 2 Rslt
Logic 1 Rslt
Default
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Bit
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
0 = False
1 = True
Содержание PowerFlex 700S
Страница 1: ...USER MANUAL Firmware Versions 1 xxx 4 002 PowerFlex 700S High Performance AC Drive Phase II Control ...
Страница 58: ...2 8 Start Up PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 Notes ...
Страница 147: ...Programming and Parameters 3 89 PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 ...
Страница 278: ...D 8 HIM Overview PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 Notes ...
Страница 316: ...Index 6 PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 ...
Страница 317: ......