Programming and Parameters
3-15
PowerFlex 700S Phase II AC Drive User Manual -
Publication 20D-UM006G-EN-P – July 2008
Parameter Data in Linear
List Format
No.
Name
Description
Values
Link
ab
le
Read
-Write
Data T
ype
1
Motor NP Volts
Set to the motor nameplate rated volts.
Units:
Default:
Min/Max:
Volt
Calculated
(1)
75/705
RW 16-bit
Integer
2
Motor NP FLA
Set to the motor nameplate rated full load amps. Range limited by three-second inverter
rating.
Units:
Default:
Min/Max:
Amps
Calculated
(1)
Calculated/Calculated
RW Real
3
Motor NP Hertz
Set to the motor nameplate rated frequency.
Units:
Default:
Min/Max:
Hz
Calculated
(1)
2.0000/500.0000
RW Real
4
Motor NP RPM
Set to the motor nameplate rated RPM.
Units:
Default:
Min/Max:
RPM
Calculated
(1)
1/30000
RW 16-bit
Integer
5
Motor NP Power
Set to the motor nameplate rated power.
Note: The unit of measure for this parameter was changed from kW to Hp for firmware version
2.03.
Units:
Default:
Min/Max:
Hp
Calculated
(1)
0.2500/3500.0000
RW 32-bit
Integer
6
Mtr NP Pwr Units
The power units shown on the motor nameplate.
Default:
Options:
0 =
0 =
1 =
“Hp”
“Hp”
“kW”
7 Motor
Poles
Set the number of motor poles indicated on the motor nameplate or manufacturer's motor
data sheet. Only even numbers of poles are allowed.
Calculation: (120 * NP Hz) / NP RPM = Poles {round down}
Note: The maximum value was changed from 60 to 128 for firmware version 4.002.
Units:
Default:
Min/Max:
Pole
4
2/128
RW 16-bit
Integer
9
Total Inertia
Time, in seconds, for a motor coupled to a load to accelerate from zero to base speed, at
rated motor torque. Calculated during auto-tune.
Units:
Default:
Min/Max:
Sec
2.0000
0.0100/655.0000
✓
RW Real
10
Speed Ref 1
Sets the speed reference that the drive should use when selected by
[Speed Ref A
[Speed Ref B Sel]. A value of 1.0 represents base speed of the motor.
Default:
Min/Max:
0.0000
-/+2200000000.0000
✓
RW Real
11
Spd Ref1 Divide
[Speed Ref 1] is divided by this number. This number can be used to scale the value of
Par 10 [Speed Ref 1].
Default:
Min/Max:
1.0000
-/+2200000000.0000
✓
RW Real
12
Speed Ref 2
Sets the speed reference that the drive should use when selected by
[Speed Ref A
[Speed Ref B Sel]. A value of 1.0 represents base speed of the motor.
Default:
Min/Max:
0.0000
-/+2200000000.0000
✓
RW Real
13
Spd Ref2 Multi
[Speed Ref 2] is multiplied by this number. This number can be used to scale the value
of Par 12 [Speed Ref 2].
Default:
Min/Max:
1.0000
-/+2200000000.0000
✓
RW Real
14
through
20
Preset Speed 1
through
Preset Speed 7
Provides an internal fixed speed command value. The preset speeds may be selected with
[Speed Ref A Sel] or
[Speed Ref B Sel].
Units:
Default:
Min/Max:
Scale:
RPM
0.0000
-/+8.0000 pu
[Motor NP RPM] = 1.0 pu
✓
RW Real
21
Speed Trim 1
Provides an additive trim value to
[Speed Ref Scale].
Units:
Default:
Min/Max:
Scale:
RPM
0.0000
-/+14112.0000
[Motor NP RPM] = 1.0 pu
✓
RW Real
22
Speed Trim 2
Provides an additive speed trim value to
[SpdRef + SpdTrm1] with a Lead/Lag filter.
The Position regulator output is linked to this parameter by default. This speed trim value
affects the speed reference input to the speed regulator.
Units:
Default:
Min/Max:
Scale:
RPM
0.0000
-/+14112.0000
[Motor NP RPM] = 1.0 pu
✓
RW Real
23
Speed Trim 3
Provides a scalable speed trim value that will be added to
[ SpdTrm1].
[SpdTrim 3 Scale] scales this value prior to the trim value affecting the speed reference.
Units:
Default:
Min/Max:
Scale:
RPM
0.0000
-/+14112.0000
[Motor NP RPM] = 1.0 pu
✓
RW Real
24
SpdTrim 3 Scale
[Speed Trim 3] is multiplied by this number. This number can be used to scale the
value of Par 23 [Speed Trim 3].
Default:
Min/Max:
1.0000
-/+1000.0000
✓
RW Real
(1)
The calculation is based on the drive frame size and input voltage
1
The calculation is based on the drive frame size and input voltage.
Содержание PowerFlex 700S
Страница 1: ...USER MANUAL Firmware Versions 1 xxx 4 002 PowerFlex 700S High Performance AC Drive Phase II Control ...
Страница 58: ...2 8 Start Up PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 Notes ...
Страница 147: ...Programming and Parameters 3 89 PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 ...
Страница 278: ...D 8 HIM Overview PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 Notes ...
Страница 316: ...Index 6 PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 ...
Страница 317: ......