Supplemental Information
A-21
PowerFlex 700S Phase II AC Drive User Manual -
Publication 20D-UM006G-EN-P – July 2008
Table A.X 480 Volt AC Input Frames 1 - 6 Drive Protection Devices
Table A.Y 480 Volt AC Input Frames 9 - 14 Drive Protection Devices
Drive
Catalog
Number
Fr
ame
HP
Rating
Input
Ratings
Dual Element
Time Delay Fuse
Non-Time
Delay Fuse
Circuit
Breaker
(3)
Motor Circuit
Protector
(5)
140M Motor Starter with Adjustable Current
Range
(6)(7)
ND
HD
Amps
kVA
Min.
(1)
Max.
(2)
Min.
(3)
Max.
(4)
Max.
(4)
Max.
(6)
Available Catalog Numbers
(8)
20DD2P1 1
1
0.75 1.6
1.4
3
6
3
8
15
3
M-C2E-B25
–
–
–
20DD3P4 1
2
1.5
2.6
2.2
4
8
4
12
15
7
M-C2E-B40
M-D8E-B40 –
–
20DD5P0 1
3
2
3.9
3.2
6
10
6
20
20
7
M-C2E-B63
M-D8E-B63 –
–
20DD8P0 1
5
3
6.9
5.7
10
15
10
30
30
15
M-C2E-C10 M-D8E-C10 M-F8E-C10 –
20DD011 1
7.5
5
9.5
7.9
15
20
15
40
40
15
M-C2E-C16 M-D8E-C16 M-F8E-C16 –
20DD014 1
10
7.5
12.5
10.4
17.5
30
17.5
50
50
20
M-C2E-C16 M-D8E-C16 M-F8E-C16 –
20DD022 1
15
10
19.9
16.6
25
50
25
80
80
30
M-C2E-C25 M-D8E-C25 M-F8E-C25 M-CMN-2500
20DD027 2
20
15
24.8
20.6
35
60
35
100
100
50
–
–
M-F8E-C32 M-CMN-4000
20DD034 2
25
20
31.2
25.9
40
70
40
125
125
50
–
–
M-F8E-C45 M-CMN-4000
20DD040 3
30
25
36.7
30.5
50
90
50
150
150
50
–
–
M-F8E-C45 M-CMN-4000
20DD052 3
40
30
47.7
39.7
60
110
60
200
200
70
–
–
–
M-CMN-6300
20DD065 3
50
40
59.6
49.6
80
125
80
250
250
100
–
–
–
M-CMN-9000
20DD077 4
60
–
72.3
60.1
100
170
100
300
300
100
–
–
–
M-CMN-9000
–
50
59.6
49.6
80
125
80
250
250
100
–
–
–
M-CMN-9000
20DD096 5
75
–
90.1
74.9
125
200
125
350
350
125
–
–
–
–
–
60
72.3
60.1
100
170
100
300
300
100
–
–
–
M-CMN-9000
20DD125 5
100 –
117
97.6
150
250
150
500
375
150
–
–
–
–
–
75
90.1
74.9
125
200
125
350
350
125
–
–
–
–
20DD156 6
125 –
146.5 121.7 200
350
200
600
450
250
–
–
–
–
–
100
131
97.6
175
250
175
500
375
250
–
–
–
–
20DD180 6
150 –
169
140.5 225
400
225
600
500
250
–
–
–
–
–
125
147
121.7 200
350
200
600
450
250
–
–
–
–
20DD248 6
200
232.8 188
300
550
300
700
700
400
–
–
–
–
150
169
140.5 225
400
225
600
500
250
–
–
–
–
(1)
Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.
(2)
Maximum protection device size is the highest rated device that supplies drive protection. For US NEC, minimum size is 125% of motor FLA. Ratings shown are
maximum.
(3)
Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(4)
Maximum allowable rating by US NEC. Exact size must be chosen for each installation.
(5)
Motor Circuit Protector - instantaneous trip circuit breaker. For US NEC minimum size is 125% of motor/drive FLA. Ratings shown are suggested. Instantaneous trip
settings must be set to US NEC code. Not to exceed 1300% FLA.
(6)
Bulletin 140M with adjustable current range should have the current trip set to the minimum range that the device will not trip.
(7)
Manual Self-Protected (Type E) Combination Motor Controller, UL listed for 208 Wye or Delta, 240 Wye or Delta, 480Y/277 or 600Y/ 347. Not UL listed for use on
480V or 600V Delta/Delta systems.
(8)
The AIC ratings of the Bulletin 140M Motor Protector may vary. See publication 140M-SG001.
Drive
Catalog
Number
Fr
ame HP Rating
Input
Ratings
Dual Element Time Delay
Fuse
Non-Time Delay Fuse
Bussmann Style
Semi-Conductor Fuse
Circuit
Breaker
(4)
Motor Circuit
Protector
(6)
ND
HD
Amps
Min.
(1)
Max.
(3)
Min.
(1)
Max.
(3)
Max.
(5)
Max.
(5)
20DD261
9
200
-
252
350
550
350
700
170M5813
700
400
-
150
207
275
450
275
600
170M5813
600
300
20DD300
9
250
-
290
400
650
400
900
170M5813
900
400
-
200
247
350
550
350
700
170M5813
700
400
20DD385
10 300
-
372
500
850
500
1100
170M5813
1100
600
-
250
302
400
650
400
900
170M5813
900
400
20DD460
10 350
-
444
600
1000
600
1300
170M8547
1300
600
-
300
388
500
850
500
1100
170M8547
1100
600
20DD500
10 450
-
483
650
1000
650
1500
170M8547
1500
700
-
350
423
550
900
550
1200
170M8547
1200
600
20DD590
11 500
-
570
750
(1 per phs)
375
(2 per phs)
1300
750
(1 per phs)
375
(2 per phs)
1700
170M5813
1700
800
-
450
524
700
(1 per phs)
350
(2 per phs)
1100
700
(1 per phs)
350
(2 per phs)
1500
170M5813
1500
700
20DD650
11 500
-
628
800
(1 per phs)
400
(2 per phs)
1400
800
(1 per phs)
400
(2 per phs)
1900
170M5813
1900
800
-
500
594
750
(1 per phs)
375
(2 per phs)
1300
750
(1 per phs)
375
(2 per phs)
1700
170M5813
1700
800
Содержание PowerFlex 700S
Страница 1: ...USER MANUAL Firmware Versions 1 xxx 4 002 PowerFlex 700S High Performance AC Drive Phase II Control ...
Страница 58: ...2 8 Start Up PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 Notes ...
Страница 147: ...Programming and Parameters 3 89 PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 ...
Страница 278: ...D 8 HIM Overview PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 Notes ...
Страница 316: ...Index 6 PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 ...
Страница 317: ......