Supplemental Information
A-19
PowerFlex 700S Phase II AC Drive User Manual -
Publication 20D-UM006G-EN-P – July 2008
Table A.V 400 Volt AC Input Frames 1 - 6 Drive Protection Devices
(3)
Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(4)
Maximum allowable rating by US NEC. Exact size must be chosen for each installation.
(5)
Motor Circuit Protector - instantaneous trip circuit breaker. For US NEC minimum size is 125% of motor/drive FLA. Ratings shown are suggested. Instantaneous trip
settings must be set to US NEC code. Not to exceed 1300% FLA.
(6)
Bulletin 140M with adjustable current range should have the current trip set to the minimum range that the device will not trip.
(7)
Manual Self-Protected (Type E) Combination Motor Controller, UL listed for 208 Wye or Delta, 240 Wye or Delta, 480Y/277 or 600Y/ 347. Not UL listed for use on
480V or 600V Delta/Delta systems.
(8)
The AIC ratings of the Bulletin 140M Motor Protector may vary. See publication 140M-SG001.
Drive
Catalog
Number
Fr
ame kW Rating
Input
Ratings
Dual Element
Time Delay Fuse
Non-Time Delay
Fuse
Circuit
Breaker
(5)
Motor Circuit
Protector
(7)
140M Motor Starter with Adjustable
Current Range
(8)(9)
ND
HD
Amps
kVA
Min.
(3)
Max.
(4)
Min.
(5)
Max.
(6)
Max.
(6)
Max.
(8)
Available Catalog Numbers
(10)
20DC2P1
1
0.75 0.55
1.8
1.3
3
6
3
8
15
3
M-C2E-B25
M-D8E-B25
–
20DC3P5
1
1.5
1.1
3.2
2.2
6
7
6
12
15
7
M-C2E-B40
M-D8E-B40
–
20DC5P0
1
2.2
1.5
4.6
3.2
6
10
6
20
20
7
M-C2E-B63
M-D8E-B63
–
20DC8P7
1
4
3.0
7.9
5.5
15
17.5
15
30
30
15
M-C2E-C10
M-D8E-C10
M-F8E-C10
20DC011
1
5.5
4
10.8
7.5
15
25
15
45
45
15
M-C2E-C16
M-D8E-C16
M-F8E-C16
20DC015
1
7.5
5.5
14.4
10.0
20
30
20
60
60
20
M-C2E-C20
M-D8E-C20
M-F8E-C20
20DC022
1
11
7.5
20.6
14.3
30
45
30
80
80
30
M-C2E-C25
M-D8E-C25
M-F8E-C25
20DC030
2
15
11
28.4
19.7
35
60
35
120
120
50
–
–
M-F8E-C32
20DC037
2
18.5 15
35.0
24.3
45
80
45
125
125
50
–
–
M-F8E-C45
20DC043
3
22
18.5
40.7
28.2
60
90
60
150
150
60
–
–
–
20DC056
3
30
22
53
36.7
70
125
70
200
200
100
–
–
–
20DC072
3
37
30
68.9
47.8
90
150
90
250
250
100
–
–
–
20DC085
(1)
4
45
–
81.4
56.4
110
200
110
300
300
150
–
–
–
–
37
68.9
47.8
90
175
90
275
300
100
–
–
–
20DC105
5
55
–
100.5 69.6
125
225
125
400
300
150
–
–
–
–
45
81.4
56.4
110
175
110
300
300
150
–
–
–
20DC125
5
55
–
121.1 83.9
150
275
150
500
375
250
–
–
–
–
45
101
63.7
125
200
125
375
375
150
–
–
–
20DC140
5
75
–
135.6 94
200
300
200
400
400
250
–
–
–
–
55
121
69.6
150
225
150
300
300
150
–
–
–
20DC170
6
90
–
164.6 114
250
375
250
600
500
250
–
–
–
–
75
136
94
200
300
200
550
400
250
–
–
–
20DC205
(2)
6
110
–
198.5 138
250
450
250
600
600
400
–
–
–
–
90
164
114
250
375
250
600
500
250
–
–
–
20DC260
6
132
–
254.7 166
350
550
350
750
750
400
–
–
–
–
110
199
138
250
450
250
600
600
400
–
–
–
(1)
20DC085 current rating is limited to 45 degrees C ambient.
(2)
20DC205 current rating is limited to 40 degrees C ambient.
(3)
Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.
(4)
Maximum protection device size is the highest rated device that supplies drive protection. For US NEC, minimum size is 125% of motor FLA. Ratings shown are
maximum.
(5)
Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(6)
Maximum allowable rating by US NEC. Exact size must be chosen for each installation.
(7)
Motor Circuit Protector - instantaneous trip circuit breaker. For US NEC minimum size is 125% of motor/drive FLA. Ratings shown are suggested. Instantaneous trip
settings must be set to US NEC code. Not to exceed 1300% FLA.
(8)
Bulletin 140M with adjustable current range should have the current trip set to the minimum range that the device will not trip.
(9)
Manual Self-Protected (Type E) Combination Motor Controller, UL listed for 208 Wye or Delta, 240 Wye or Delta, 480Y/277 or 600Y/ 347. Not UL listed for use on
480V or 600V Delta/Delta systems.
(10)
The AIC ratings of the Bulletin 140M Motor Protector may vary. See publication 140M-SG001.
Содержание PowerFlex 700S
Страница 1: ...USER MANUAL Firmware Versions 1 xxx 4 002 PowerFlex 700S High Performance AC Drive Phase II Control ...
Страница 58: ...2 8 Start Up PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 Notes ...
Страница 147: ...Programming and Parameters 3 89 PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 ...
Страница 278: ...D 8 HIM Overview PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 Notes ...
Страница 316: ...Index 6 PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 ...
Страница 317: ......