Programming and Parameters
3-19
PowerFlex 700S Phase II AC Drive User Manual -
Publication 20D-UM006G-EN-P – July 2008
77
Spd Ref TP Sel
Enter or write a value to select speed reference data displayed in
[Spd Ref TP Data]
[Spd Ref TP RPM].
Note: The values for options 7, 8, & 9 were changed to “Reserved” for firmware version 2.04.
Default:
Options:
0 =
0 =
1 =
2 =
3 =
4 =
5 =
6 =
7 =
8 =
9 =
10 =
11 =
“Zero”
“Zero”
12 = “S Crv Match”
“User Ref”
13 = “S Array size”
“Logic Select”
14 = “S Array Indx”
“Lgc Sel Ref”
15 = “Reserved”
“Ramp Spd Ref”
16 = “Scl Ext Trim”
“Ramp In”
17 = “Trim FiltOut”
“Filt Spd Ref”
18 = “Ref w/Trim”
“Reserved”
19 = “Amp Lim2 In”
“Reserved”
20 = “Amp LimStat2”
“Reserved”
21 = “Amp Lim2 Out”
“Amp Lim Stat”
22 = “FTD Ramp Out”
“Ramp Match”
23 = “Reserved”
78
Spd Ref TP RPM
Displays the value selected in
[Spd Ref TP Sel] in RPM. This display should only be
used if the selected value is floating point data.
Units:
Default:
Min/Max:
Scale:
RPM
0.0000
-/+8.0000
[Motor NP RPM] = 1.0 pu
RO Real
79
Spd Ref TP Data
Displays the value selected in
[Spd Ref TP Sel]. This display should only be used if the
selected value is integer data.
Default:
Min/Max:
0
-/+32768
RO 16-bit
Integer
81
Spd Reg P Gain
Sets the proportional gain of the speed regulator. This value is automatically calculated
based on the bandwidth setting in
[Spd Reg BW]. Proportional gain may be manually
adjusted by setting Par 90 [Spd Reg BW] to a value of zero. Units are (per unit torque) / (per
unit speed).
The maximum value for Par 81 [Spd Reg P Gain] = Par 90 [Spd Reg BW] *
[Total Inertia]
Note: The Max. value was increased from 600.0000 for firmware version 3.01.
Default:
Min/Max:
20.0000
0.0000/3000.0000
✓
RW Real
82
Spd Reg I Gain
Sets the integral gain of the speed regulator. This value is automatically calculated based on
the bandwidth setting in
[Spd Reg BW]. Integral gain may be manually adjusted by
setting Par 90 [Spd Reg BW] to a value of zero. Units are (per unit torque/sec) / (per unit
speed).
Units:
Default:
Min/Max:
/Sec
50.0000
0.0000/100000.0000
✓
RW Real
84
SpdReg AntiBckup
By setting this parameter to 0.3, the drive will not over shoot to a step response. This
parameter has no affect on the drive's response to load changes. The recommended setting is
0.1000 to 0.5000.
Note: This parameter was changed to non-linkable for firmware version 3.01.
Default:
Min/Max:
0.0000
0.0000/0.5000
RW Real
No.
Name
Description
Values
Linkab
le
R
ead-Wr
ite
Da
ta
T
ype
Total Inertia
(Par 9)
Maximum Speed Regulator
Bandwidth (Par 90)
Maximum Speed Regulator
Proportional Gain (Par 81)
0.01
475 (0.5 mSec)
4.75
0.01
650 (0.25 mSec)
6.50
0.01
30 (sensorless mode)
0.03
2.0
475 (0.5 mSec)
950
2.0
650 (0.25 mSec)
1300
2.0
30 (sensorless mode)
60
Under-
S
hoot
Over-
S
hoot
Over-
S
hoot
Under-
S
hoot
Error
Reference
Feed
ba
ck,
S
pdReg AntiBck
u
p = 0.0
Feed
ba
ck,
S
pdReg AntiBck
u
p = 0.
3
Error
Содержание PowerFlex 700S
Страница 1: ...USER MANUAL Firmware Versions 1 xxx 4 002 PowerFlex 700S High Performance AC Drive Phase II Control ...
Страница 58: ...2 8 Start Up PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 Notes ...
Страница 147: ...Programming and Parameters 3 89 PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 ...
Страница 278: ...D 8 HIM Overview PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 Notes ...
Страница 316: ...Index 6 PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 ...
Страница 317: ......