3-110
Programming and Parameters
PowerFlex 700S Phase II AC Drive User Manual -
Publication 20D-UM006G-EN-P – July 2008
1070
Logic 2B Bit
[Logic 2B Data] for the second input to Logic Block 2.
Note: To invert the selected input enter the desired bit as negative. Use -32 to invert bit 0.
Default:
Min/Max:
0
-31/32
RW 16-bit
Integer
1071
Compare 1A
Sets input A for the Compare 1 function. The compare function allows the user to compare
two values. The results of the compare are displayed in
[Logic/Cmpr State].
Available functions are ( A </= B , A >/= B ).
Default:
Min/Max:
0.0000
-/+2200000000.0000
✓
RW Real
1072
Compare 1B
Sets input B for the Compare 1. The compare functions allow the user to compare two values.
The results of the compare are displayed in
[Logic/Cmpr State].
Available functions are ( A </= B , A >/= B ).
Default:
Min/Max:
0.0000
-/+2200000000.0000
✓
RW Real
1073
Compare 2A
Sets input A for the Compare 2. The compare functions allow the user to compare two values.
The results of the compare are displayed in
[Logic/Cmpr State].
Available functions are ( A </= B , A >/= B ).
Default:
Min/Max:
0.0000
-/+2200000000.0000
✓
RW Real
1074
Compare 2B
Sets input B for the Compare 2. The compare functions allow the user to compare two values.
The results of the compare are displayed in
[Logic/Cmpr State].
Available functions are ( A </= B , A >/= B ).
Default:
Min/Max:
0.0000
-/+2200000000.0000
✓
RW Real
1086
MOP Control
Motor Operated Potentiometer (MOP) control and configuration.
•
Bit 0 “Increase”, if set, increments the MOP level (output) from
[MOP Rate] to
[MOP High Limit].
•
Bit 1 “Decrease”, if set, decrements the MOP level (output) from Par 1087 [MOP Rate] to
[MOP Low Limit].
•
Bit 2 “Reset”, if set, resets the MOP level (output) to zero and bit 0 “Increment” and bit 1 “Decrease” are inhibited.
•
Bit 3 “Reset @ Stop”, if set, resets the MOP level (output) to zero when stop is set.
•
Bit 4 “Reset @ PwrLs”, if set, resets the MOP level (output) to zero when power is lost.
Note: If either bit 3 or bit 4 is not set, the MOP level (output) will be saved until bit 2 “Reset” is set.
1087
MOP Rate
Sets the rate of change (increment or decrement) for the MOP. The setting 0.1/sec will equate
to an increment or decrement of 0.1 for every second active. If this is used for the speed
reference, that equals 10% of base speed every second for a total of 10 seconds to reach
base speed reference.
Units:
Default:
Min/Max:
Sec
0.1000 Sec
0.0000/2200000000.0000
✓
RW Real
1088
MOP High Limit
Sets the upper limit for the MOP output. The MOP cannot be incremented above this level.
Units:
Default:
Min/Max:
Sec
1.0000 Sec
0.0000/2200000000.0000
✓
RW Real
1089
MOP Low Limit
Sets the lower limit for the MOP output. The MOP cannot be decremented below this level.
Units:
Default:
Min/Max:
Sec
-1.0000 Sec
-2200000000.0000/0.0000
✓
RW Real
1090
MOP Level Real
Actual output value of the MOP as a real number. This value is also found in the speed
reference selection. A value of 1.0 equals base motor speed.
Units:
Default:
Min/Max:
Sec
0.0000
-/+2200000000.0000
RO Real
1091
MOP Scale Dint
Set this value for scaling of the Dint MOP output. The MOP is calculated and controlled as a
Real value MOP. Use this scaler to adjust for an integer value. Use this parameter to scale the
conversion from
[MOP Level Dint].
Default:
Min/Max:
1.0000
-/+2200000000.0000
✓
RW Real
1092
MOP Level DInt
Actual output value of the MOP as a DInt number. This value is scaled by
Scale DInt].
Default:
Min/Max:
0.0000
-/+2147483648
RO 32-bit
Integer
1093
1094
1095
Anlg In1LossCnfg
Anlg In2LossCnfg
Anlg In3LossCnfg
Selects drive action when an analog input signal loss is detected. Signal loss is defined as an
analog signal less than 1 V or 2 mA. The signal loss event ends and normal operation
resumes when the input signal is greater than or equal to 1.5 V or 3 mA.
Note: This parameter was added for firmware version 3.01.
Default:
Options:
0 =
0 =
1 =
2 =
3 =
“Disabled”
“Disabled”
4 = “Set Input Hi”
“Fault”
5 = “Goto Preset1”
“Hold Input”
6 = “Hold OutFreq”
“Set Input Lo”
No.
Name
Description
Values
Linkab
le
R
ead-Wr
ite
Da
ta
T
ype
Options
Re
set @
PwrLs
Re
set @
Stop
Re
set
De
cr
ease
In
cr
ea
se
Default
0
0
0
0
0
Bit
4
3
2
1
0
Содержание PowerFlex 700S
Страница 1: ...USER MANUAL Firmware Versions 1 xxx 4 002 PowerFlex 700S High Performance AC Drive Phase II Control ...
Страница 58: ...2 8 Start Up PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 Notes ...
Страница 147: ...Programming and Parameters 3 89 PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 ...
Страница 278: ...D 8 HIM Overview PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 Notes ...
Страница 316: ...Index 6 PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 ...
Страница 317: ......