3-76
Programming and Parameters
PowerFlex 700S Phase II AC Drive User Manual -
Publication 20D-UM006G-EN-P – July 2008
528
Run Boost
Sets the boost level for steady state or deceleration when “V/Hz” mode is selected.
Note: This parameter was added for firmware version 2.03.
Units:
Default:
Min/Max:
VAC
50.0
0.0/1150.0
RW 16-bit
Integer
529
Break Voltage
Sets the voltage the drive will output at
[Break Frequency].
Note: This parameter was added for firmware version 2.03.
Units:
Default:
Min/Max:
VAC
1150.0
0.0/6900.0
RW 16-bit
Integer
530
Break Frequency
Sets the frequency the drive will output at
[Break Voltage].
Note: This parameter was added for firmware version 2.03.
Units:
Default:
Min/Max:
Hz
150.0
0.0/400.0
RW 16-bit
Integer
531
Maximum Voltage
Sets the highest voltage the drive will output.
Note: This parameter was added for firmware version 2.03.
Units:
Default:
Min/Max:
VAC
460.0
60.0/690.0
RW 16-bit
Integer
532
Maximum Freq
Sets the highest frequency the drive will output. This parameter is a function of
[Motor
NP Hertz].
Note: This parameter was added for firmware version 2.03.
Units:
Default:
Min/Max:
Hz
(
[Motor NP Hertz] * 2) + 10Hz
Par 3 [Motor NP Hertz] + 10 Hz/420.0
RW 16-bit
Integer
533
SlewRateTimeLimt
Defines the time limit in seconds during which torque producing voltage (Vqs) regulator
output variations are limited by each slew rate at the transition where the Vqs regulator
turns on. The same time limit is applied at the transition to the slip regulator when the slip
regulator turns on. A value of zero disables the slew rate function on both the Vqs regulator
output and the slip regulator output. Par 553 defines the slew rate for the slip regulator and
[IdsCmd Slew Rate] defines the slew rate for the Vqs regulator.
Notes: This parameter was added for firmware version 3.01. This parameter was renamed
from “Flux Gain Adjust” to “SlewRateTimeLimit”, the default value was changed to “10.0”
and the minimum value was changed to “0.0” for firmware version 4.001.
Default:
Min/Max:
0.0
0.0/1126.0
RW 16-bit
Integer
537
SrLssAngleStblty
Adjusts the electrical angle to maintain stable motor operation. An increase in the value
increases the angle adjustment.
Default:
Min/Max:
51.0
0.0/32767.0
RW 16-bit
Integer
538
SrLss VoltStblty
Adjusts the voltage to maintain stable motor operation. An increase in the value increases
the output voltage adjustment.
Default:
Min/Max:
93.0
0.0/32767.0
RW 16-bit
Integer
539
SrLss StbltyFilt
The coefficient is used to adjust the bandwidth of a low pass filter. The smaller the value of
the coefficient, the lower the bandwidth of the filter.
Default:
Min/Max:
3250.0
0.0/32767.0
RW 16-bit
Integer
540
V/Hz Status
Indicates the limit status of the V/Hz Control Operation.
Note: This parameter was added form firmware version 2.03.
541
SrLss Angl Comp
Not currently used.
Note: This parameter was added for future use - not active for use with firmware version
2.03 and above.
Default:
Min/Max:
0.0
+/- 16384
RW 16-bit
Integer
542
SrLss Volt Comp
Not currently used.
Note: This parameter was added for future use - not active for use with firmware version
2.03 and above.
Units:
Default:
Min/Max:
Volts
100.0
+/- 1000.0
RW 16-bit
Integer
544
External DB Res
Sets the resistance value of an external dynamic braking resistor. This value is used to
determine the power applied to the resistor and thus calculate its temperature.
Note: This parameter was added for firmware version 4.001.
Units:
Default:
Min/Max:
Ohms
49.0
0.1/500.0
RW Real
545
Bus Reg Ki
Sets the responsiveness of the bus regulator.
Note: This parameter was added for firmware version 2.03.
Default:
Min/Max:
450.0
0.0/100000
RW 16-bit
Integer
546
Bus Reg Kp
Proportional gain for the bus regulator. Used to adjust regulator response.
Note: This parameter was added for firmware version 2.03.
Default:
Min/Max:
1500.0
0.0/10000.0
RW 16-bit
Integer
547
Bus Reg Kd
Derivative gain for the bus regulator. Used to control regulator overshoot.
Note: This parameter was added for firmware version 2.03.
Default:
Min/Max:
1000.0
0.0/10000.0
RW 16-bit
Integer
No.
Name
Description
Values
Linkab
le
R
ead-Wr
ite
Da
ta
T
ype
Options
Rese
rv
ed
Rese
rv
ed
Rese
rv
ed
Rese
rv
ed
Rese
rv
ed
Rese
rv
ed
Rese
rv
ed
Rese
rv
ed
Rese
rv
ed
Rese
rv
ed
Rese
rv
ed
Rese
rv
ed
Rese
rv
ed
Rese
rv
ed
Bus V
olt Lim
Cur
ren
t Lim
Default
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Bit
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
0 = False
1 = True
Содержание PowerFlex 700S
Страница 1: ...USER MANUAL Firmware Versions 1 xxx 4 002 PowerFlex 700S High Performance AC Drive Phase II Control ...
Страница 58: ...2 8 Start Up PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 Notes ...
Страница 147: ...Programming and Parameters 3 89 PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 ...
Страница 278: ...D 8 HIM Overview PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 Notes ...
Страница 316: ...Index 6 PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 ...
Страница 317: ......