3-30
Programming and Parameters
PowerFlex 700S Phase II AC Drive User Manual -
Publication 20D-UM006G-EN-P – July 2008
173
Setpt1 TripPoint
Provides the midpoint for operation of bit 16 “At Setpt 1” of
[Logic Status].
Units:
Default:
Min/Max:
P.U.
0.1000
-/+8.0000 pu
✓
RW Real
174
Setpt 1 Limit
Creates a tolerance - hysteresis band around the value in
[Setpt1 TripPoint].
•
Turn-on level for ascending data = TripPoint - Limit.
•
Turn-off level for ascending data = Tri 2(Limit).
•
Turn-on level for descending data = Tri Limit.
•
Turn-off level for descending data = TripPoint - 2(Limit).
Units:
Default:
Min/Max:
P.U.
0.0100
0.0000/0.5000
✓
RW Real
175
Setpt 2 Data
Provides data for comparison to
[Setpt2 TripPoint], driving bit 17 “Above Setpt 2” of
[Logic Status]. For more information, please see
.
Units:
Default:
Min/Max:
P.U.
0.0000
-/+8.0000 pu
✓
RW Real
176
Setpt2 TripPoint
Provides the midpoint for operation of bit 17 “Above Setpt 2” of
[Logic Status].
Units:
Default:
Min/Max:
P.U.
0.2000
-/+8.0000 pu
✓
RW Real
177
Setpt 2 Limit
Creates a tolerance - hysteresis band around the value in
[Setpt2 TripPoint].
For positive setpoints:
•
Turn-on level = TripPoint
•
Turn-off level = TripPoint - Limit.
For negative setpoints:
•
Turn-on level = TripPoint
•
Turn-off level = Tri Limit.
Units:
Default:
Min/Max:
P.U.
0.0100
0.0000/0.5000
✓
RW Real
178
PI TP Sel
Enter or write a value to select Process Control PI data displayed by
[PI TP Data].
The values for options 1 & 8 were changed to “Reserved” for firmware version 2.04.
Default:
Options:
0 =
0 =
1 =
2 =
3 =
4 =
5 =
6 =
“Zero”
“Zero”
7 = “Status Hold”
“Reserved”
8 = “Reserved”
“LPF Output”
9 = “Reset Status”
“P Gain Term”
10 = “Time Axis En”
“Reg Output”
11 = “Enbl Status”
“On Intg Lim”
12 = “Out Max Lim”
“On Out Limit”
13 = “Out Min Lim”
179
PI TP Data
[PI TP Sel].
Units:
Default:
Min/Max:
P.U.
0.0000
-/+8.0000 pu
RO Real
180
PI Output
The final output of the Process Control regulator. A value of 1 can represent either base
motor speed, motor rated torque, or 100% for some external function.
Units:
Default:
Min/Max:
P.U.
0.0000
-/+8.0000 pu
RO Real
181
PI Reference
The reference input for the process control regulator. A value of 1 can represent either base
motor speed, motor rated torque, or 100% for some external function.
Units:
Default:
Min/Max:
P.U.
0.0000
-/+8.0000 pu
✓
RW Real
182
PI Feedback
The feedback input for the process control regulator. A value of 1 can represent either base
motor speed, motor rated torque, or 100% for some external function.
Units:
Default:
Min/Max:
P.U.
0.0000
-/+8.0000 pu
✓
RW Real
183
PI Error
Displays the error of the process trim reference minus the process trim feedback.
Units:
Default:
Min/Max:
P.U.
0.0000
-/+8.0000 pu
RO Real
184
PI Lpass Filt BW
Sets the bandwidth of a single pole filter applied to the error input of the Process Control
regulator. The input to the filter is the difference between
[PI Reference] and
[PI Feedback]. The output of this filter is used as the input to the process control regulator.
Units:
Default:
Min/Max:
R/S
0.0000
0.0000/500.0000
✓
RW Real
185
PI Preload
Presets the integrator of the Process Control regulator.
Units:
Default:
Min/Max:
P.U.
0.0000
-/+8.0000 pu
✓
RW Real
186
PI Prop Gain
Controls the proportional gain of the Process Control regulator. If the proportional gain is 1.0,
the regulator output equals 1 pu for 1 pu error.
Default:
Min/Max:
8.0000
0.0000/200.0000
✓
RW Real
187
PI Integ Time
Controls the integral gain of the Process Control regulator. If the integrator time is 1.0, the
regulator output equals 1 pu in 1 second for 1 pu error.
Units:
Default:
Min/Max:
/Sec
8.0000
0.0000/4000.0000
✓
RW Real
188
PI Integ HLim
The high limit of the integral gain channel for the Process Control regulator. A value of 1 can
represent either base motor speed, motor rated torque, or 100% for some external function.
Units:
Default:
Min/Max:
P.U.
0.1000
0.0000/8.0000
✓
RW Real
189
PI Integ LLim
The low limit of the integral gain channel for the Process Control regulator. A value of 1 can
represent either base motor speed, motor rated torque, or 100% for some external function.
Units:
Default:
Min/Max:
P.U.
-0.1000
-8.0000/0.0000
✓
RW Real
No.
Name
Description
Values
Linkab
le
R
ead-Wr
ite
Da
ta
T
ype
Содержание PowerFlex 700S
Страница 1: ...USER MANUAL Firmware Versions 1 xxx 4 002 PowerFlex 700S High Performance AC Drive Phase II Control ...
Страница 58: ...2 8 Start Up PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 Notes ...
Страница 147: ...Programming and Parameters 3 89 PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 ...
Страница 278: ...D 8 HIM Overview PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 Notes ...
Страница 316: ...Index 6 PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 ...
Страница 317: ......