Protective Trip and Warning Functions
Chapter 6
Full Load Amps Setting
FLA (Parameter 171) is one of two parameters that affect the E300 Electronic
Overload Relay’s thermal capacity utilization algorithm. you enters the motor’s
full-load current rating into this parameter.
Table 162 - FLA (Parameter 171)
FLA2 (Parameter 177) is provided for programming the high-speed FLA value in
two-speed motor applications. Activating FLA2 is described in
.
Table 163 - FLA2 (Parameter 177)
USA and Canada Guidelines
•
Motor Service Factor ≥ 1.15: For motors with a service factor rating of
1.15 or greater, program the FLA setting to the full-load current rating on
the printed nameplate.
•
Motor Service Factor < 1.15: For motors with a service factor rating less
than 1.15, program the FLA setting to 90% of the full-load current rating
on the printed nameplate.
•
Wye-Delta (Y-Δ) Applications: Follow the application’s service factor
instructions, except divide the full-load current rating on the printed
nameplate by 1.73.
FLA (Parameter 171)
Default Value
0.50
(0.5…30 A Sensing Modules)
6.00
(6…60 A Sensing Modules)
10.00
(10…100 A Sensing Modules)
20.00
(20…200 A Sensing Modules)
Minimum Value
0.50
Maximum Value
65535.00
Parameter Type
UDINT
Size (Bytes)
4
Scaling Factor
100
Units
Amps
FLA2 (Parameter 177)
Default Value
0.50
(0.5…30 A Sensing Modules)
6.00
(6…60 A Sensing Modules)
10.00
(10…100 A Sensing Modules)
20.00
(20…200 A Sensing Modules)
Minimum Value
0.50
Maximum Value
65535.00
Parameter Type
UDINT
Size (Bytes)
4
Scaling Factor
100
Units
Amps
Содержание Allen-Bradley E300
Страница 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Страница 124: ...124 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 4 System Operation and Configuration Notes...
Страница 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Страница 292: ...292 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 6 Protective Trip and Warning Functions...
Страница 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Страница 372: ...372 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 8 Metering and Diagnostics...
Страница 460: ...460 Rockwell Automation Publication 193 UM015D EN P February 2015 Appendix A Specifications Notes...
Страница 501: ...Rockwell Automation Publication 193 UM015D EN P February 2015 501 Parameter List AppendixB Notes...
Страница 502: ...502 Rockwell Automation Publication193 UM015D EN P November 2013 Appendix B Parameter List...
Страница 545: ......