Protective Trip and Warning Functions
Chapter 6
Table 206 - L3 Under Current Warning Level (Parameter 274)
Line Over Current Protection
For non-motor applications when the measured current is greater than a specific
level for a specific phase may indicate an electrical malfunction, such as bad
resistive heater element. Such conditions could harm the power system over a
period of time, which could lead to loss of production.
The E300 Electronic Overload Relay can monitor for an overcurrent condition
per phase with its Line Over Current Trip and Warning function to detect for a
rapid over current in a specific phase to minimize damage and loss of production.
Over Current Inhibit Time
Over Current Inhibit Time (Parameter 275) allows you to inhibit an L1, L2, and
L3 Over Current trip and warning from occurring during a load starting
sequence. It is adjustable from 0…250 seconds.
Table 207 - Over Current Inhibit Time (Parameter 275)
L1 Over Current Trip
The E300 Electronic Overload Relay trips with a L1 Over Current indication if:
•
No trip currently exists
•
L1 Over Current Trip is enabled
•
Current is present
Default Value
40
Minimum Value
10
Maximum Value
100
Parameter Type
USINT
Size (Bytes)
1
Scaling Factor
1
Units
%FLA
IMPORTANT
The L3 Under Current Warning function does not include a time delay feature.
Once the Under Current Inhibit Timer has expired, the L3 Under Current
Warning indication is instantaneous.
Default Value
10
Minimum Value
0
Maximum Value
250
Parameter Type
USINT
Size (Bytes)
1
Scaling Factor
1
Units
Seconds
Содержание Allen-Bradley E300
Страница 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Страница 124: ...124 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 4 System Operation and Configuration Notes...
Страница 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Страница 292: ...292 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 6 Protective Trip and Warning Functions...
Страница 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Страница 372: ...372 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 8 Metering and Diagnostics...
Страница 460: ...460 Rockwell Automation Publication 193 UM015D EN P February 2015 Appendix A Specifications Notes...
Страница 501: ...Rockwell Automation Publication 193 UM015D EN P February 2015 501 Parameter List AppendixB Notes...
Страница 502: ...502 Rockwell Automation Publication193 UM015D EN P November 2013 Appendix B Parameter List...
Страница 545: ......