264
Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Chapter 6
Protective Trip and Warning Functions
•
The measured analog input signal is greater than the Analog Module 1 –
Channel 01 Trip Level for a time period greater than the Analog Module 1
– Channel 01 Over Level Trip Delay.
If the E300 Electronic Overload Relay trips on an Analog Module 1 – Channel
01 Over Level, the:
•
TRIP/WARN LED status indicator flashes a red 4-long / 2-short blink
pattern
•
Bit 1 in Analog Trip Status (Parameter 8) sets to 1
•
Bit 0 in Device Status 0 (Parameter 20) sets to 1
•
Any relay outputs configured as a Trip Relay open
•
Any relay outputs configured as a Control Relay open
•
Any relay outputs configured as a Trip Alarm close
•
Any relay outputs configured as a Normal Relay are placed in their
Protection Fault state (if so programmed)
Analog Module 1 – Channel 01 Over Level Trip Delay
Analog Module 1 – Channel 01 Over Level Trip Delay (Parameter 452) allows
you to define the time period an Analog Module 1 – Channel 01 Over Level
condition must be present before a trip occurs. It is adjustable from 0.1…25.0
seconds.
IMPORTANT
The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output
Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and
Digital Module 4 Output Relays are defined by the respective parameters:
•
Output PT00 Protection Fault Action (Parameter 304)
•
Output PT00 Protection Fault Value (Parameter 305)
•
Output PT01 Protection Fault Action (Parameter 310)
•
Output PT01 Protection Fault Value (Parameter 311)
•
Output PT02 Protection Fault Action (Parameter 316)
•
Output PT02 Protection Fault Value (Parameter 317)
•
Output Digital Module 1 Protection Fault Action (Parameter 322)
•
Output Digital Module 1 Protection Fault Value (Parameter 323)
•
Output Digital Module 2 Protection Fault Action (Parameter 328)
•
Output Digital Module 2 Protection Fault Value (Parameter 329)
•
Output Digital Module 3 Protection Fault Action (Parameter 334)
•
Output Digital Module 3 Protection Fault Value (Parameter 335)
•
Output Digital Module 4 Protection Fault Action (Parameter 340)
•
Output Digital Module 4 Protection Fault Value (Parameter 342)
Содержание Allen-Bradley E300
Страница 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Страница 124: ...124 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 4 System Operation and Configuration Notes...
Страница 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Страница 292: ...292 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 6 Protective Trip and Warning Functions...
Страница 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Страница 372: ...372 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 8 Metering and Diagnostics...
Страница 460: ...460 Rockwell Automation Publication 193 UM015D EN P February 2015 Appendix A Specifications Notes...
Страница 501: ...Rockwell Automation Publication 193 UM015D EN P February 2015 501 Parameter List AppendixB Notes...
Страница 502: ...502 Rockwell Automation Publication193 UM015D EN P November 2013 Appendix B Parameter List...
Страница 545: ......