78
Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Chapter 4
System Operation and Configuration
Input Pt03 Assignment (Parameter 199)
Input Pt03 Assignment (Parameter 199) allows you to assign this digital input
for the following functions:
Table 42 - Input Pt03 Assignment (Parameter 199)
Input Pt04 Assignment (Parameter 200)
Input Pt04 Assignment (Parameter 200) allows you to assign this digital input
for the following functions:
Table 43 - Input Pt04 Assignment (Parameter 200)
Value
Assignment
Description
0
Normal
Function as a digital input
1
Trip Reset
Reset the E300 when it is in a tripped state
2
Remote Trip
Force the E300 to go into a tripped state
3
Activate FLA2
Use the value in FLA2 Setting (Parameter 177) for the current-based protection
algorithms
4
Force Snapshot
Force the E300 to update its Snapshot log
5
Emergency Start
Issue an Emergency Start command
6
Test Mode
Enable Test Mode monitoring
7
L1 Line Loss Arm
Activate L1 Line Loss Protection
8
L2 Line Loss Arm
Activate L2 Line Loss Protection
9
L3 Line Loss Arm
Activate L3 Line Loss Protection
10
L1 L2 Line Loss Arm
Activate L1 and L2 Line Loss Protection
11
L2 L3 Line Loss Arm
Activate L2 and L3 Line Loss Protection
12
L1 L3 Line Loss Arm
Activate L1 and L3 Line Loss Protection
13
L1 L2 L3 Line Loss Arm Activate L1, L2, and L3 Line Loss Protection
Value
Assignment
Description
0
Normal
Function as a digital input
1
Trip Reset
Reset the E300 when it is in a tripped state
2
Remote Trip
Force the E300 to go into a tripped state
3
Activate FLA2
Use the value in FLA2 Setting (Parameter 177) for the current-based protection
algorithms
4
Force Snapshot
Force the E300 to update its Snapshot log
5
Emergency Start
Issue an Emergency Start command
6
Test Mode
Enable Test Mode monitoring
7
L1 Line Loss Arm
Activate L1 Line Loss Protection
8
L2 Line Loss Arm
Activate L2 Line Loss Protection
9
L3 Line Loss Arm
Activate L3 Line Loss Protection
10
L1 L2 Line Loss Arm
Activate L1 and L2 Line Loss Protection
11
L2 L3 Line Loss Arm
Activate L2 and L3 Line Loss Protection
12
L1 L3 Line Loss Arm
Activate L1 and L3 Line Loss Protection
13
L1 L2 L3 Line Loss Arm Activate L1, L2, and L3 Line Loss Protection
Содержание Allen-Bradley E300
Страница 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Страница 124: ...124 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 4 System Operation and Configuration Notes...
Страница 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Страница 292: ...292 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 6 Protective Trip and Warning Functions...
Страница 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Страница 372: ...372 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 8 Metering and Diagnostics...
Страница 460: ...460 Rockwell Automation Publication 193 UM015D EN P February 2015 Appendix A Specifications Notes...
Страница 501: ...Rockwell Automation Publication 193 UM015D EN P February 2015 501 Parameter List AppendixB Notes...
Страница 502: ...502 Rockwell Automation Publication193 UM015D EN P November 2013 Appendix B Parameter List...
Страница 545: ......