Rockwell Automation Publication 193-UM015D-EN-P - February 2015
485
Parameter List
Appendix
B
Voltage Setup
352
VoltageMode
C.VoltageMode
Voltage Wiring
Mode
USINT
1
1
0= Delta
1= Wye
2= DeltaPTDelta2Wye
3= WyePTDelta2Wye
4= DeltaPTWye2Delta
5= WyePTWye2Delta
0
353
PTPrimary
C.PTPrimary
Potential
Transformer
Primary Rating
UINT
2
1
1
65535
480
354
PTSecondary
C.PTSecondary
Potential
Transformer
Secondary Rating
UINT
2
1
1
540
480
355
UVInhibitTime
C.UnderVoltageInhibitTime
Under Voltage
Inhibit Time
USINT
1
1
0
250
10
Second
s
356
UVTripDelay
C.UnderVoltageTripDelay
Under Voltage Trip
Delay
USINT
1
10
1
250
10
Second
s
357
UVTripLevel
C.UnderVoltageTripLimit
Under Voltage Trip
Level
UINT
2
10
0
65535
1000
Volt
358
UVWarningLevel
C.UnderVoltageWarnLimit
Under Voltage
Warning Level
UINT
2
10
0
65535
4000
Volt
359
OVInhibitTime
C.OverVoltageInhibitTime
Over Voltage
Inhibit Time
USINT
1
1
0
250
10
Second
s
360
OVTripDelay
C.OverVoltageTripDelay
Over Voltage Trip
Delay
USINT
1
10
1
250
10
Second
s
361
OVTripLevel
C.OverVoltageTripLimit
Over Voltage Trip
Level
UINT
2
10
0
65535
5000
Volt
362
OVWarningLevel
C.OverVoltageWarnLimit
Over Voltage
Warning Level
UINT
2
10
0
65535
4900
Volt
363
PhRotInhibitTime
C.PhaseRotationInhibitTime
Phase Rotation
Inhibit Time
USINT
1
1
0
250
10
Second
s
364
PhaseRotTripType
C.PhaseRotationTripType_0
C.PhaseRotationTripType_1
Voltage Phase
Rotation Trip Type
USINT
1
1
1
0=
NoRotation
1= ABC
2= ACB
1
365
VIBInhibitTime
C.VoltageImbalanceInhibitTime
Voltage Imbalance
Inhibit Time
USINT
1
1
0
250
10
Second
s
Voltage Setup
(continued)
366
VIBTripDelay
C.VoltageImbalanceTripDelay
Voltage Imbalance
Trip Delay
USINT
1
10
1
250
10
Second
s
367
VIBTripLevel
C.VoltageImbalanceTripLimit
Voltage Imbalance
Trip Level
USINT
1
1
0
100
85
%
368
VIBWarningLevel
C.VoltageImbalanceWarnLimit
Voltage Imbalance
Warning Level
USINT
1
1
0
100
75
%
369
UFInhibitTime
C.UnderFrequencyInhibitTime
Under Frequency
Inhibit Time
USINT
1
1
0
250
10
Second
s
370
UFTripDelay
C.UnderFrequencyTripDelay
Under Frequency
Trip Delay
USINT
1
10
1
250
10
Second
s
371
UFTripLevel
C.UnderFrequencyTripLimit
Under Frequency
Trip Level
USINT
1
1
46
65
57
Hz
372
UFWarningLevel
C.UnderFrequencyWarnLimit
Under Frequency
Warning Level
USINT
1
1
46
65
58
Hz
373
OFInhibitTime
C.OverFrequencyInhibitTime
Over Frequency
Inhibit Time
USINT
1
1
0
250
10
Second
s
374
OFTripDelay
C.OverFrequencyTripDelay
Over Frequency
Trip Delay
USINT
1
10
1
250
10
Second
s
375
OFTripLevel
C.OverFrequencyTripLimit
Over Frequency
Trip Level
USINT
1
1
46
65
63
Hz
376
OFWarningLevel
C.OverFrequencyWarnLimit
Over Frequency
Warning Level
USINT
1
1
46
65
62
Hz
Group
Param
No.
Parameter Name
Device Profile Tag Name
Description
Type
Data Size
(bytes)
Scale
Factor
Min
Max
Default Units
Содержание Allen-Bradley E300
Страница 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Страница 124: ...124 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 4 System Operation and Configuration Notes...
Страница 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Страница 292: ...292 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 6 Protective Trip and Warning Functions...
Страница 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Страница 372: ...372 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 8 Metering and Diagnostics...
Страница 460: ...460 Rockwell Automation Publication 193 UM015D EN P February 2015 Appendix A Specifications Notes...
Страница 501: ...Rockwell Automation Publication 193 UM015D EN P February 2015 501 Parameter List AppendixB Notes...
Страница 502: ...502 Rockwell Automation Publication193 UM015D EN P November 2013 Appendix B Parameter List...
Страница 545: ......