494
Rockwell Automation Publication 193-UM015D-EN-P - November 2013
Appendix B
Parameter List
Analog2 Setup
(continued)
487
InAMod2Ch2Format
C.Analog2.Ch02InputFormat_0
C.Analog2.Ch02InputFormat_1
C.Analog2.Ch02InputFormat_2
Assignment for
Analog Module 2
Input Channel 02
Data Format
USINT
1
1
0= EngUnits
1= EngUnitsTimes10
2= RawProportional
3= ScaledForPID
0
488
InAMod2C2TmpUnit
C.Analog2.Ch02InputTempMode
Assignment for
Analog Module 2
Input Channel 02
Temperature Units
USINT
1
1
0=DegreesC
1=DegreesF
0
489
InAMod2C2FiltFrq
C.Analog2.Ch02InputFilter_0
C.Analog2.Ch02InputFilter_1
C.Analog2.Ch02InputFilter_2
Assignment
Analog Module 2
Input Channel 02
Filter Freq
USINT
1
1
0=17Hz
1=4Hz
2=62Hz
3=470Hz
0
490
InAMod2C2OpCktSt
C.Analog2.Ch02InputOpenWire_0
C.Analog2.Ch02InputOpenWire_1
Indicates Analog
Module 2 Input
Channel 02 Open
Circuit State
USINT
1
1
0=Upscale
1=Downscale
2=Zero
0
491
InAnMod2Ch2RTDEn C.Analog2.Ch02InputTwoWireRTD
Enable
Analog
Module 2 Input
Channel 02 to
function with RTD
BOOL
1
1
0=3-wire
1=2-wire
0
492
InAMod2C2TripDly
C.Analog2.Ch02InputTripDelay
Analog Module 2
Input Channel 02
Trip Delay
USINT
1
10
0
250
10
Second
s
493
InAMod2C2TripLvl
C.Analog2.Ch02InputTripLimit
Level (in selected
Units) where
Analog Input
generates a trip
UINT
2
1
-32768
32767
0
494
InAMod2C2WarnLvl
C.Analog2.Ch02InputWarnLimit
Level (in selected
Units) where
Analog Input
generates a
warning
UINT
2
1
-32768
32767
0
495
OutAnMod2Type
C.Analog2.Ch00OutputRangeType_0
C.Analog2.Ch00OutputRangeType_1
C.Analog2.Ch00OutputRangeType_2
C.Analog2.Ch00OutputRangeType_3
Assignment for
Analog Module 2
Output function.
USINT
1
1
0= Disabled
1= 4To20mA
2= 0To20mA
3= 0To10Volts
4=1To5 Volts
5=OTo5 Volts
0
496
OutAnMod2Select
C.Analog2.Ch00OutputMode
Assignment of
parameter data
value to drive
Analog Module 2
Output
USINT
1
1
0= AveragePctFLA
1= ScaledAvgPctFLA
2= PercentTCU
3= GFCurrent
4= CurrentUnbalance
5= AvgLLVoltage
6=VoltLLUnbalance
7= TotalkW
8= TotalkVA
9= TotalkVAR
10= TotalPF
11= UserDLXData
0
497
OutAnMod2EFltAct
C.Analog2.Ch00OutputFaultMode_0
C.Analog2.Ch00OutputFaultMode_1
Analog Module 2
Output action on
an Expansion Bus
fault
USINT
1
1
0= Zero
1= Maximum
2= Minimum
3= HoldLastState
0
Group
Param
No.
Parameter Name
Device Profile Tag Name
Description
Type
Data Size
(bytes)
Scale
Factor
Min
Max
Default Units
Содержание Allen-Bradley E300
Страница 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Страница 124: ...124 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 4 System Operation and Configuration Notes...
Страница 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Страница 292: ...292 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 6 Protective Trip and Warning Functions...
Страница 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Страница 372: ...372 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 8 Metering and Diagnostics...
Страница 460: ...460 Rockwell Automation Publication 193 UM015D EN P February 2015 Appendix A Specifications Notes...
Страница 501: ...Rockwell Automation Publication 193 UM015D EN P February 2015 501 Parameter List AppendixB Notes...
Страница 502: ...502 Rockwell Automation Publication193 UM015D EN P November 2013 Appendix B Parameter List...
Страница 545: ......