Rockwell Automation Publication 193-UM015D-EN-P - February 2015
379
EtherNet/IP Communications
Chapter 9
Assign Network Parameters Via a Web Browser and MAC Scanner
Software
If you do not have access to a DHCP software utility, you can assign network
parameters via a web browser (for example, Microsoft® Internet Explorer) and
Media Access Control (MAC) scanner software (for example, MAC Scanner
from Colasoft® - http://www.colasoft.com/). Follow these steps to configure the
module using this method.
1.
Locate and identify the MAC ID printed on the label of the E300
Electronic Overload Relay EtherNet/IP Communication Module. This
address has a format that is similar to: 00-0b-db-14-55-35
2.
Connect the E300 Electronic Overload Relay EtherNet/IP
Communication Module to the same wide area network (WAN) as your
personal computer.
3.
Initiate the MAC scanner software.
4.
Select the appropriate subnet to scan for available MAC addresses.
5.
Scan the Subnet for all available MAC addresses
.
6.
Identify the IP address assigned to the MAC ID of the E300 Electronic
Overload Relay EtherNet/IP Communication Module. The IP address
will have a format that is similar to 192.168.0.100.
Other Factors to Consider When Assigning Network Parameters
There are other factors to consider when assigning network parameters, which
include:
•
Network isolation from or integration into the plant/enterprise network.
•
Network size. For large networks, even isolated networks, it might be more
convenient and safer to use a BOOTP/DHCP server rather than RSLinx
software. The BOOTP/DHCP server also limits the possibility of
assigning duplicate IP addresses.
•
Company policies and procedures that are associated with plant floor
network installation and maintenance.
•
Level of involvement by information technology personnel in plant floor
network installation and maintenance.
•
Type of training that is offered to control engineers and maintenance
personnel.
Содержание Allen-Bradley E300
Страница 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Страница 124: ...124 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 4 System Operation and Configuration Notes...
Страница 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Страница 292: ...292 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 6 Protective Trip and Warning Functions...
Страница 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Страница 372: ...372 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 8 Metering and Diagnostics...
Страница 460: ...460 Rockwell Automation Publication 193 UM015D EN P February 2015 Appendix A Specifications Notes...
Страница 501: ...Rockwell Automation Publication 193 UM015D EN P February 2015 501 Parameter List AppendixB Notes...
Страница 502: ...502 Rockwell Automation Publication193 UM015D EN P November 2013 Appendix B Parameter List...
Страница 545: ......