Rockwell Automation Publication 193-UM015D-EN-P - February 2015
223
Protective Trip and Warning Functions
Chapter 6
Table 272 - Under kVAR Generated Warn Level (Parameter 397)
Over kVAR Generated Trip
The E300 Electronic Overload Relay trips with an Over kVAR Generated
indication if:
•
No trip currently exists
•
Over kVAR Generated Trip is enabled
•
Current is present
•
Voltage is present
•
Over kVAR Generated Inhibit Time has expired
•
The total reactive power (kVAR) generated is greater than the Over
•
kVAR Generated Trip Level for a time period greater than the Over kVAR
Generated Trip Delay.
If the E300 Electronic Overload Relay trips on an over reactive power (kVAR)
generated, the:
•
TRIP/WARN LED status indicator flashes a red 2-long / 6-short blink
pattern
•
Bit 5 in Power Trip Status (Parameter 6) sets to 1
•
Bit 0 in Device Status 0 (Parameter 20) sets to 1
•
Any relay outputs configured as a Trip Relay open
•
Any relay outputs configured as a Control Relay open
•
Any relay outputs configured as a Trip Alarm close
•
Any relay outputs configured as a Normal Relay are placed in their
Protection Fault state (if so programmed)
Default Value
0.000
Minimum Value
0.000
Maximum Value
2000000.000
Parameter Type
DINT
Size (Bytes)
4
Scaling Factor
1000
Units
kVAR
IMPORTANT
The Under kVAR Generated Warning function does not include a time delay
feature. Once the Under kVAR generated Inhibit Time has expired, the Under
kVAR Generated Warning indication is instantaneous.
Содержание Allen-Bradley E300
Страница 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Страница 124: ...124 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 4 System Operation and Configuration Notes...
Страница 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Страница 292: ...292 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 6 Protective Trip and Warning Functions...
Страница 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Страница 372: ...372 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 8 Metering and Diagnostics...
Страница 460: ...460 Rockwell Automation Publication 193 UM015D EN P February 2015 Appendix A Specifications Notes...