66
Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Chapter 4
System Operation and Configuration
Table 21 - Invalid Configuration Cause (Parameter 39)
The Trip/Warn LED on the Communication Module and Operator Stations will
be flashing a pattern of red, 3 long and 8 short blinks, and bits 0 and 2 in Device
Status 0 (Parameter 20) are set to 1 when the device is in Invalid Configuration
Mode.
Table 22 - Invalid Configuration Mode Bit Function Detail — Device Status 0 (Parameter 20)
To return to Operation/Run Mode, place a valid configuration value in the
parameter identified by Invalid Configuration Parameter (Parameter 38) and
Invalid Configuration Cause (Parameter 39). Reset the trip state of the E300
Electronic Overload Relay by pressing the blue reset button on the
Communication Module, via network communications, with the internal web
server of the EtherNet/IP communications module, or by an assigned digital
input.
Option Match
Due to the modular nature of the E300 Electronic Overload Relay, you can
enable the Option Match feature to ensure that the options that were expected
for the motor protection application are the ones that are present on the E300
Code
Description
0
No Error
1
Value over maximum value
2
Value under minimum value
3
Illegal value
4
L3 Current detected (for single-phase applications)
5
CopyCat error
Bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Function
X
Trip Present
X
Warning Present
X
Invalid Configuration
X
Current Present
X
GFCurrent Present
X
Voltage Present
X
Emergency Start Enabled
X
DeviceLogix Enabled
X
Feedback Timeout Enabled
X
Operator Station Present
X
Voltage Sensing Present
X
Intern Ground Fault Sensing Present
X
Extern Ground Fault Sensing Present
X
PTC Sensing
X
Ready
Reserved
Содержание Allen-Bradley E300
Страница 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Страница 124: ...124 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 4 System Operation and Configuration Notes...
Страница 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Страница 292: ...292 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 6 Protective Trip and Warning Functions...
Страница 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Страница 372: ...372 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 8 Metering and Diagnostics...
Страница 460: ...460 Rockwell Automation Publication 193 UM015D EN P February 2015 Appendix A Specifications Notes...
Страница 501: ...Rockwell Automation Publication 193 UM015D EN P February 2015 501 Parameter List AppendixB Notes...
Страница 502: ...502 Rockwell Automation Publication193 UM015D EN P November 2013 Appendix B Parameter List...
Страница 545: ......