Protective Trip and Warning Functions
•
Bit 1 in Device Status 0 (Parameter 20) sets to 1
•
Any relay outputs configured as Warning Alarm close
Overload Warning Level (Parameter 175) can be used as an alert for an
impending overload trip and is adjustable from 0…100% TCU.
Table 168 - Overload Warning Level (Parameter 175)
Time to Trip
When the measured motor current exceeds the trip rating of the E300 Electronic
Overload Relay, Overload Time to Trip (Parameter 2) indicates the estimated
time remaining before an overload trip occurs. When the measured current is
below the trip rating, the Overload Time to Trip value is reported as 9,999
seconds.
Table 169 - Overload Time to Trip (Parameter 2)
Time To Reset
After an overload trip, the E300 Electronic Overload Relay reports the time
remaining until the device can be reset through Overload Time to Reset
(Parameter 3). When the % Thermal Capacity Utilized value falls to or below the
Overload Reset Level (Parameter 174), the Overload Time to Reset value
indicates zero until the overload trip is reset. After an overload trip is reset, the
Overload Time to Reset value is reported as 0 seconds.
Overload Warning Level (Parameter 175)
Default Value
85
Minimum Value
0
Maximum Value
100
Parameter Type
USINT
Size (Bytes)
1
Scaling Factor
1
Units
%TCU
Overload Time to Trip (Parameter 2)
Default Value
9999
Minimum Value
0
Maximum Value
9999
Parameter Type
UINT
Size (Bytes)
2
Scaling Factor
1
Units
Seconds
Содержание Allen-Bradley E300
Страница 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Страница 124: ...124 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 4 System Operation and Configuration Notes...
Страница 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Страница 292: ...292 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 6 Protective Trip and Warning Functions...
Страница 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Страница 372: ...372 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 8 Metering and Diagnostics...
Страница 460: ...460 Rockwell Automation Publication 193 UM015D EN P February 2015 Appendix A Specifications Notes...
Страница 501: ...Rockwell Automation Publication 193 UM015D EN P February 2015 501 Parameter List AppendixB Notes...
Страница 502: ...502 Rockwell Automation Publication193 UM015D EN P November 2013 Appendix B Parameter List...
Страница 545: ......