72
Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Chapter 4
System Operation and Configuration
Digital I/O expansion module set to Digital Module 4. There are three different
types of Digital I/O expansion modules. Place the value of the expected Digital
I/O expansion module set to Digital Module 4 into Parameter 228. A value of (0)
disables the Option Match feature for this Digital I/O expansion module. A
value of (1),
“No Digital I/O Expansion Module ”
, makes the Digital I/O
expansion module set to Digital Module 4 not allowed on the Expansion Bus and
prevents you from connecting a Digital I/O expansion module set to Digital
Module 4 to the E300 Electronic Overload Relay system.
Table 32 - Digital I/O Expansion Module 4 Type (Parameter 228)
Analog I/O Expansion Module 1 Type (Parameter 229)
The E300 Electronic Overload Relay supports up to four additional Analog I/O
expansion modules. This parameter configures the Option Match feature for the
Analog I/O expansion module set to Analog Module 1. There is one type of
Analog I/O expansion module. Place the value of the expected Analog I/O
expansion module set to Analog Module 1 into Parameter 229. A value of (0)
disables the Option Match feature for this Analog I/O expansion module. A
value of (1),
“No Analog I/O Expansion Module”
, makes the Analog I/O
expansion module set to Analog Module 1 not allowed on the Expansion Bus and
prevents you from connecting an Analog I/O expansion module set to Analog
Module 1 to the E300 Electronic Overload Relay system.
Table 33 - Analog I/O Expansion Module 1 Type (Parameter 229)
Code
Description
Digital I/O Expansion Module Cat. No.
0
Ignore
—
1
No Digital I/O Expansion Module (Digital I/O Expansion
Module Not Allowed)
—
2
4 Inputs, 24V DC / 2 Relay Outputs
193-EXP-DIO-42-24D
3
4 Inputs, 110-120V AC 50/60Hz / 2 Relay Outputs
193-EXP-DIO-42-120
4
4 Inputs, 220-240V AC 50/60Hz / 2 Relay Outputs
193-EXP-DIO-42-240
Code
Description
Analog I/O Expansion Module Cat. No.
0
Ignore
—
1
No Analog I/O Expansion Module (Analog I/O Expansion
Module Not Allowed)
—
2
3 Universal Analog Inputs / 1 Analog Output
193-EXP-AIO-31
Содержание Allen-Bradley E300
Страница 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Страница 124: ...124 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 4 System Operation and Configuration Notes...
Страница 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Страница 292: ...292 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 6 Protective Trip and Warning Functions...
Страница 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Страница 372: ...372 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 8 Metering and Diagnostics...
Страница 460: ...460 Rockwell Automation Publication 193 UM015D EN P February 2015 Appendix A Specifications Notes...
Страница 501: ...Rockwell Automation Publication 193 UM015D EN P February 2015 501 Parameter List AppendixB Notes...
Страница 502: ...502 Rockwell Automation Publication193 UM015D EN P November 2013 Appendix B Parameter List...
Страница 545: ......