Table 20 - Run Mode Bit Function Detail — Device Status 0 (Parameter 20)
Test Mode
Test Mode is used by installers of motor control centers who are testing and
commissioning motor starters with an automation system. A digital input of the
E300 Electronic Overload Relay is assigned to monitor the motor control center
enclosure’s Test Position. The Input Assignments (Parameters 196…201) are
described later in this chapter.
Anyone commissioning motor starters in an automation system can put their
motor control center enclosure into the Test Position to activate Test Mode and
verify that the digital inputs and relay outputs of the E300 Electronic Overload
Relay are operating properly with the motor starter without energizing power to
the motor. If the E300
Electronic Overload Relay senses current or voltage in Test
Mode, the E300 Electronic Overload Relay will generate a Test Mode Trip.
Invalid Configuration Mode
Invalid Configuration Mode is an active mode for the E300 Electronic Overload
Relay in which the E300 is in a tripped state due to invalid configuration data.
Invalid Configuration Parameter (Parameter 38) indicates the parameter number
that is causing the fault. Invalid Configuration Cause (Parameter 39) identifies
the reason for Invalid Configuration Mode.
Bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Function
X
Trip Present
X
Warning Present
X
Invalid Configuration
X
Current Present
X
GFCurrent Present
X
Voltage Present
X
Emergency Start Enabled
X
DeviceLogix Enabled
X
Feedback Timeout Enabled
X
Operator Station Present
X
Voltage Sensing Present
X
Intern Ground Fault Sensing Present
X
Extern Ground Fault Sensing Present
X
PTC Sensing
X
Ready
Reserved
Содержание Allen-Bradley E300
Страница 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Страница 124: ...124 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 4 System Operation and Configuration Notes...
Страница 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Страница 292: ...292 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 6 Protective Trip and Warning Functions...
Страница 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Страница 372: ...372 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 8 Metering and Diagnostics...
Страница 460: ...460 Rockwell Automation Publication 193 UM015D EN P February 2015 Appendix A Specifications Notes...
Страница 501: ...Rockwell Automation Publication 193 UM015D EN P February 2015 501 Parameter List AppendixB Notes...
Страница 502: ...502 Rockwell Automation Publication193 UM015D EN P November 2013 Appendix B Parameter List...
Страница 545: ......