392
Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Chapter 9
EtherNet/IP Communications
Automatic Device Configuration enables the Logix controller to manage device
configuration data. Every time a Logix controller establishes a connection with a
device, the Logix controller will download that device’s configuration data. This
allows users to save commissioning time by preprogramming a device offline
using RSLogix 5000 or Studio 5000. It also removes the need for maintenance
personnel to have a computer and special programming software when replacing
a device.
Shown in the following pages are three examples and the steps necessary to
configure a Logix controller for I/O messaging.
•
Pre-configured E300 Electronic Overload Relay Logix Integration with
Add-on Profile
•
Offline E300 Electronic Overload Relay Logix Integration with Add-on
Profile
•
Offline E300 Electronic Overload Relay Integration with a Generic Profile
Preconfigured E300 Electronic Overload Relay Logix Integration with
an Add-On Profile
The E300 Add-on Profile for RSLogix 5000 and Studio 5000 software
automatically enables Automatic Device Configuration. The Logix controller
will overwrite any existing E300 Electronic Overload Relay configuration data
ATTENTION:
If an
Upload
command is not performed while discovering
modules or manually adding a E300 Electronic Overload Relay online to a
ControlLogix project, any preconfigured E300 Electronic Overload Relay
configuration data will not be retained.
Preconfigured E300 Electronic Overload Relay Logix Integration with an
for information on how to upload configuration
data when adding an E300 Electronic Overload Relay to a ControlLogix project
online.
ATTENTION:
If an Upload command is not performed while manually adding
an E300 Electronic Overload Relay offline in an RSLogix 5000 or Studio 5000
project, any preconfigured E300 Electronic Overload Relay configuration data
will not be retained when downloading the project to the Logix controller.
Preconfigured E300 Electronic Overload Relay Logix Integration with an
for information on how to upload configuration
data when adding an E300 Electronic Overload Relay to an RSLogix 5000 or
Studio 5000 project offline.
Содержание Allen-Bradley E300
Страница 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Страница 124: ...124 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 4 System Operation and Configuration Notes...
Страница 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Страница 292: ...292 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 6 Protective Trip and Warning Functions...
Страница 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Страница 372: ...372 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 8 Metering and Diagnostics...
Страница 460: ...460 Rockwell Automation Publication 193 UM015D EN P February 2015 Appendix A Specifications Notes...
Страница 501: ...Rockwell Automation Publication 193 UM015D EN P February 2015 501 Parameter List AppendixB Notes...
Страница 502: ...502 Rockwell Automation Publication193 UM015D EN P November 2013 Appendix B Parameter List...
Страница 545: ......