Rockwell Automation Publication 193-UM015D-EN-P - February 2015
121
System Operation and Configuration
Chapter 4
Analog Module 4 – Input Channel 02 Temperature Unit
Analog Module 4 – Input Channel 02 Temperature Unit (Parameter 550)
defines the temperate unit for RTD sensor readings.
Table 151 - Analog Module 4 – Input Channel 02 Temperature Unit (Parameter 550)
Analog Module 4 – Input Channel 02 Filter Frequency
Analog Module 4 – Input Channel 02 Filter Frequency (Parameter 551) defines
update rate for the analog module’s input channels.
Table 152 - Analog Module 4 – Input Channel 02 Filter Frequency (Parameter 551)
Analog Module 4 – Input Channel 02 Open Circuit State
Analog Module 4 – Input Channel 02 Open Circuit State (Parameter 552)
defines what the input channel reports when the input channel has an open
circuit. Open circuit detection is always enabled for this input channel.
Table 153 - Analog Module 4 – Input Channel 02 Open Circuit State (Parameter 552)
Analog Module 4 – Input Channel 02 RTD Type Enable
Analog Module 4 – Input Channel 02 RTD Type Enable (Parameter 556)
defines the type of RTD to monitor when the input channel type is configured to
scan an RTD sensor.
Table 154 - Analog Module 4 – Input Channel 02 RTD Type Enable (Parameter 556)
Analog Module 4 – Output Channel 00 Type
Analog Module 4 – Output Channel 00 Type (Parameter 557) defines the type
of analog signal that Output Channel 00 of Analog Module 4 will be providing.
Value
Assignment
Description
0
DegreesC
Report RTD Temperature Data in °C
1
DegreesF
Report RTD Temperature Data in °F
Value
Assignment
Description
0
17 Hz
Analog to Digital Conversion Update Frequency of 17 Hz
1
4 Hz
Analog to Digital Conversion Update Frequency of 4 Hz
2
62 Hz
Analog to Digital Conversion Update Frequency of 62 Hz
3
470 Hz
Analog to Digital Conversion Update Frequency of 470Hz
Value
Assignment
Description
0
Upscale
Reports the high limit of the input channel type
1
Downscale
Reports the low limit of the input channel type
2
Zero
Reports zero
Value
Assignment
Description
0
3-Wire
Scan a 3-wire RTD sensor
1
2-Wire
Scan a 2-wire RTD sensor
Содержание Allen-Bradley E300
Страница 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Страница 124: ...124 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 4 System Operation and Configuration Notes...
Страница 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Страница 292: ...292 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 6 Protective Trip and Warning Functions...
Страница 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Страница 372: ...372 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 8 Metering and Diagnostics...
Страница 460: ...460 Rockwell Automation Publication 193 UM015D EN P February 2015 Appendix A Specifications Notes...
Страница 501: ...Rockwell Automation Publication 193 UM015D EN P February 2015 501 Parameter List AppendixB Notes...
Страница 502: ...502 Rockwell Automation Publication193 UM015D EN P November 2013 Appendix B Parameter List...
Страница 545: ......