Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Chapter 4
System Operation and Configuration
Expansion Bus Warning
Expansion Bus Warning is enabled by setting Control Warning Enable
(Parameter 192) bit 10 to 1. When communications is disrupted between the
Control Module and digital and/or analog expansion I/O modules, the E300
Electronic Overload Relay will go into a warning state in which the Trip/Warn
LED on the Communication Module and Operator station will blink a yellow 3
long and 11 short blinking pattern.
Table 51 - Expansion Bus Warning Bit Function Detail— Control Warning Enable (Parameter 192)
To return to Operation/Run Mode, verify that the expansion bus cables are
properly plugged into the Bus In and Bus Out ports of all of the expansion
modules. When all of the expansion I/O modules’ status LEDs are solid green,
the warning state of the E300 Electronic Overload Relay will automatically clear.
Emergency Start
In an emergency, it may be necessary to start a motor even if a protection fault or
a communication fault exists. The trip condition may be the result of a thermal
overload condition or the number of starts exceeded its configuration. These
conditions can be overridden using the Emergency Start feature of the E300
Electronic Overload Relay.
To enable the Emergency Start feature in the E300 Electronic Overload Relay set
the Emergency Start Enable (Parameter 216) to Enable.
Bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Function
Reserved
X
PTC Warning Enable
X
DeviceLogix Warning Enable
X
Operator Station Warning Enable
Reserved
Reserved
Reserved
Reserved
X
Option Match Warning Enable
X
Feedback Timeout Warning Enable
X
Expansion Bus Warning Enable
X
Number Of Starts Warning Enable
X
Operating Hours Warning Enable
Reserved
IMPORTANT
Activating Emergency Start inhibits overload and blocked start protection.
Running in this mode can cause equipment overheating and fire.
Содержание Allen-Bradley E300
Страница 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Страница 124: ...124 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 4 System Operation and Configuration Notes...
Страница 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Страница 292: ...292 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 6 Protective Trip and Warning Functions...
Страница 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Страница 372: ...372 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 8 Metering and Diagnostics...
Страница 460: ...460 Rockwell Automation Publication 193 UM015D EN P February 2015 Appendix A Specifications Notes...
Страница 501: ...Rockwell Automation Publication 193 UM015D EN P February 2015 501 Parameter List AppendixB Notes...
Страница 502: ...502 Rockwell Automation Publication193 UM015D EN P November 2013 Appendix B Parameter List...
Страница 545: ......