492
Rockwell Automation Publication 193-UM015D-EN-P - November 2013
Appendix B
Parameter List
Analog1 Setup
(continued)
467
OutAnMod1IdlActn
C.Analog1.Ch00OutputProtectionFaultMode_0
C.Analog1.Ch00OutputProtectionFaultMode_1
Analog Module 1
Output action on
comms idle
USINT
1
1
0= Zero
1= Maximum
2= Minimum
3= Hold Last State
0
Analog2 Setup
468
InAnMod2Ch00Type
C.Analog2.Ch00InputRangeType_0
C.Analog2.Ch00InputRangeType_1
C.Analog2.Ch00InputRangeType_2
C.Analog2.Ch00InputRangeType_3
C.Analog2.Ch00InputRangeType_4
Assignment for
Analog Module 2
Input Channel 00
function
USINT
1
1
0= Disabled
1= 4To20mA
2= 0To20mA
3= 0To10Volts
4= 1To5Volts
5= 0To5Volts
6= 100Pt385
7= 200Pt385
8= 500Pt385
9= 1000Pt385
10=100Pt3916
11= 200Pt3916
12= 500Pt3916
13= 1000Pt3916
14= 10Cu426
15= 120Ni618
16= 120Ni672
17= 604NiFe518
18= 150ohm
19= 1000ohm
20 = 3000ohm
21= 6000ohm
0
469
InAMod2Ch0Format
C.Analog2.Ch00InputFormat_0
C.Analog2.Ch00InputFormat_1
C.Analog2.Ch00InputFormat_2
Assignment for
Analog Module 2
Input Channel 00
Data Format
USINT
1
1
0= EngUnits
1= EngUnitsTimes10
2= RawProportional
3= ScaledForPID
0
470
InAMod2C0TmpUnit
C.Analog2.Ch00InputTempMode
Assignment for
Analog Module 2
Input Channel 00
Temperature Units
USINT
1
1
0=DegreesC
1=DegreesF
0
471
InAMod2C0FiltFrq
C.Analog2.Ch00InputFilter_0
C.Analog2.Ch00InputFilter_1
C.Analog2.Ch00InputFilter_2
Assignment for
Analog Module 2
Input Channel 00
Filter Freq
USINT
1
1
0=17Hz
1=4Hz
2=62Hz
3=470Hz
0
472
InAMod2C0OpCktSt
C.Analog2.Ch00InputOpenWire_0
C.Analog2.Ch00InputOpenWire_1
Indicates Analog
Module 2 Input
Channel 00 Open
Circuit State
USINT
1
1
0=Upscale
1=Downscale
2=Zero
0
473
InAnMod2Ch0RTDEn
C.Analog2.Ch00InputTwoWireRTD
Enable Analog
Module 2 Input
Channel 00 to
function with RTD
BOOL
1
1
0=3-wire
1=2-wire
0
474
InAMod2C0TripDly
C.Analog2.Ch00InputTripDelay
Analog Module 2
Input Channel 00
Trip Delay
USINT
1
10
0
250
10
Second
s
475
InAMod2C0TripLvl
C.Analog2.Ch00InputTripLimit
Level (in selected
Units) where
Analog Input
generates a trip
UINT
2
1
-32768
32767
0
476
InAMod2C0WarnLvl
C.Analog2.Ch00InputWarnLimit
Level (in selected
Units) where
Analog Input
generates a
warning
UINT
2
1
-32768
32767
0
Group
Param
No.
Parameter Name
Device Profile Tag Name
Description
Type
Data Size
(bytes)
Scale
Factor
Min
Max
Default Units
Содержание Allen-Bradley E300
Страница 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Страница 124: ...124 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 4 System Operation and Configuration Notes...
Страница 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Страница 292: ...292 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 6 Protective Trip and Warning Functions...
Страница 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Страница 372: ...372 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 8 Metering and Diagnostics...
Страница 460: ...460 Rockwell Automation Publication 193 UM015D EN P February 2015 Appendix A Specifications Notes...
Страница 501: ...Rockwell Automation Publication 193 UM015D EN P February 2015 501 Parameter List AppendixB Notes...
Страница 502: ...502 Rockwell Automation Publication193 UM015D EN P November 2013 Appendix B Parameter List...
Страница 545: ......