380
Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Chapter 9
EtherNet/IP Communications
If the Rockwell Automation DHCP server is used in an uplinked subnet where
an enterprise DHCP server exists, a module may get an address from the
enterprise server before the Rockwell Automation utility even sees the module. In
this case, disconnect the uplink to set the address and configure the module to
retain its static address before reconnecting to the uplink. This is not a problem if
you have node names configured in the module and leave DHCP enabled.
Web Server
As a security precaution the embedded web server of the E300 Electronic
Overload Relay EtherNet/IP Communication Module is disabled by default. To
temporarily enable the web server to make it permanently available, you must
enter into Administration Mode. To do this, set the rotary dials that are located
underneath the front cover of the E300 Electronic Overload Relay EtherNet/IP
Communication Module to 000 and cycle power. The device will then go online
with the IP Address used at the time of the previous start-up.
Web Server Security and System Password
The E300 EtherNet/IP Communication Module’s web server allows you to view
any diagnostic and parameter information. Security measures are built into the
web server to deter a malicious user from making any unwanted EtherNet/IP
system changes and E300 configuration parameter edits. When you attempt to
make an EtherNet/IP system change or E300 configuration parameter edit, you
will be prompted to enter a user name and password.
System User Name
The user name
Administrator
(case sensitive) is the only user name that allows
you to make EtherNet/IP system changes or E300 configuration parameter edits.
System Password
For EtherNet/IP Communication Modules with firmware v1.003, the default
password is <blank>.
Содержание Allen-Bradley E300
Страница 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Страница 124: ...124 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 4 System Operation and Configuration Notes...
Страница 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Страница 292: ...292 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 6 Protective Trip and Warning Functions...
Страница 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Страница 372: ...372 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 8 Metering and Diagnostics...
Страница 460: ...460 Rockwell Automation Publication 193 UM015D EN P February 2015 Appendix A Specifications Notes...
Страница 501: ...Rockwell Automation Publication 193 UM015D EN P February 2015 501 Parameter List AppendixB Notes...
Страница 502: ...502 Rockwell Automation Publication193 UM015D EN P November 2013 Appendix B Parameter List...
Страница 545: ......