70
Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Chapter 4
System Operation and Configuration
Operator Station Type (Parameter 224)
The E300 Electronic Overload Relay offers two different types of operator
stations. Place the value of the expected operator station into Parameter 224. A
value of (0) disables the Option Match feature for the operator station. A value of
(1),
“No Operator Station”
, makes the operator station not allowed on the
Expansion Bus and prevents you from connecting an operator station to the E300
Electronic Overload Relay system.
Table 28 - Operator Station Type (Parameter 224)
Digital I/O Expansion Module 1 Type (Parameter 225)
The E300 Electronic Overload Relay supports up to four additional Digital I/O
expansion modules. This parameter configures the Option Match feature for the
Digital I/O expansion module set to Digital Module 1. There are three different
types of Digital I/O expansion modules. Place the value of the expected Digital
I/O expansion module set to Digital Module 1 into Parameter 225. A value of (0)
disables the Option Match feature for this Digital I/O expansion module. A
value of (1),
“No Digital I/O Expansion Module”
, makes the Digital I/O
expansion module set to Digital Module 1 not allowed on the Expansion Bus and
prevents you from connecting a Digital I/O expansion module set to Digital
Module 1 to the E300 Electronic Overload Relay system.
Table 29 - Digital I/O Expansion Module 1 Type (Parameter 225)
Code
Description
Operator Station Cat. No.
0
Ignore
—
1
No Operator Station (Operator Station Not Allowed)
—
2
Control Station
193-EOS-SCS
3
Diagnostic Station with LCD
193-EOS-SDS
Code
Description
Digital I/O Expansion Module Cat. No.
0
Ignore
—
1
No Digital I/O Expansion Module (Digital I/O Expansion
Module Not Allowed)
—
2
4 Inputs, 24V DC / 2 Relay Outputs
193-EXP-DIO-42-24D
3
4 Inputs, 110-120V AC 50/60Hz / 2 Relay Outputs
193-EXP-DIO-42-120
4
4 Inputs, 220-240V AC 50/60Hz / 2 Relay Outputs
193-EXP-DIO-42-240
Содержание Allen-Bradley E300
Страница 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Страница 124: ...124 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 4 System Operation and Configuration Notes...
Страница 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Страница 292: ...292 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 6 Protective Trip and Warning Functions...
Страница 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Страница 372: ...372 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 8 Metering and Diagnostics...
Страница 460: ...460 Rockwell Automation Publication 193 UM015D EN P February 2015 Appendix A Specifications Notes...
Страница 501: ...Rockwell Automation Publication 193 UM015D EN P February 2015 501 Parameter List AppendixB Notes...
Страница 502: ...502 Rockwell Automation Publication193 UM015D EN P November 2013 Appendix B Parameter List...
Страница 545: ......