Operating the Drive
Page
7-28
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D
8
9
10
11
A
B
C
D
1
2
3
4
5
6
7
E
Settings
All 890CD and 890SD Drives
ALL
890 drives in the system
MUST
have their internal EMC "Y" caps to earth disconnected.
Set the demanded boosted DC link voltage (DC VOLTS DEMAND) appropriately
for the drive voltage rating. This is given in the separate table below.
Refer to Appendix D for a full description of the REGEN CONTROL function block
parameters.
890 4-Q Regen Drive:
Create an application using the DSE 890 Configuration Tool.
Refer to page 7-30 for wiring details.
sv 1.x
MMI Menu Map
1
SETUP
2
MOTOR CONTROL
3
MOTOR DATA
CONTROL
MODE
LEAKAGE
INDUC
sv 3.x
MMI Menu Map
1
SETUP
2
MOTOR CONTROL
3
MOTOR DATA
LEAKAGE
INDUC
sv 3.x
MMI Menu Map
1
SETUP
2
DRIVE SETUP
3
DRIVE CONFIG
CONTROL
MODE
Set the CONTROL MODE parameter to "4-Q REGEN".
Set the LEAKAGE INDUC parameter to the value of the total line choke inductance. Refer to page 7-44.