890SD Standalone Drive
Page
5-38
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D
8
9
10
11
A
B
C
D
1
2
3
4
5
6
7
E
SET-UP PARAMETERS
PREF
6511/6901
Display
Default
Brief Description
V/Hz
SV
CLV
4-Q PMAC
27.04
MOTOR
VOLTAGE
product code
dependent
Enter the motor
nameplate voltage at
base frequency
x x x
27.07
NAMEPLATE
RPM
product code
dependent
Enter the motor
nameplate full-load
rated speed. This is the
motor speed in rpm at
base frequency minus
full load slip.
x x x
27.09
MOTOR POLES
product code
dependent
0 : 2 pole
1 : 4 pole
2 : 6 pole
3 : 8 pole
4 : 10 pole
5 : 12 pole
Enter the number of
motor poles from the
motor nameplate
x x x
27.08
MOTOR
CONNECTION
product code
dependent
0 : DELTA
1 : STAR
Enter the type of motor
connection
x x