Programming
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D
Page
D-81
8
9
10
A
B
C
D
E
1
2
3
4
5
6
7
MOTOR INDUCTION
SETUP::MOTOR CONTROL::MOTOR INDUCTION
Designed for all Motor Control Mode, except PMAC Control Mode.
In this function block you enter the details of the motor under control and any available motor nameplate information.
The Autotune feature will determine the MAG CURRENT, STATOR RES, LEAKAGE INDUC, MUTUAL INDUC and ROTOR
TIME CONST motor model parameter.
The OVERLOAD parameter determines the allowed level of motor overload. This can be especially useful when operating
with motors smaller than the drive rating.
Note
Do not attempt to control motors whose rated current is less than 25% of the drive rated current. Poor motor control
or Autotune problems may occur if you do.
Parameter Descriptions
POWER
PREF: 27.02
Default: 1.5 kW
Range
:
0.00 to 3000.00kW
This parameter contains the motor nameplate power.
* BASE FREQUENCY
PREF: 27.03
Default: 50.0 Hz
Range
:
7.5 to 1000.0Hz
This parameter contains the motor nameplate base frequency. Refer to FLUXING, page D-54.
* MOTOR VOLTAGE
PREF: 27.04
Default: 230.0 V
Range:
0.0 to 575.0V
This parameter contains the motor nameplate voltage at base frequency. Refer to V MASTER SIMLATR, page D-183.
MOTOR CURRENT
PREF: 27.05
Default: 6.26 A
Range: 0.00 to 3276.70 A
This parameter contains the motor nameplate full-load line current.
MAG CURRENT
PREF: 27.06
Default: 2.50 A
Range
:
0.00 to 3276.70 A
This parameter contains the motor model no-load line current as determined by the auto-tune.