Keypad Menus
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D
Page
9-27
8
9
10
11
A
B
C
D
1
2
3
4
5
6
7
E
QUICK SETUP MENU
890CD Common Bus Drive & 890SD Standalone Drive
PREF
6511/6901
Display
Description
Range
Default
27.06
(induction
motor
only)
MAG CURRENT
This parameter contains the motor model no-
load line current as determined by the
Autotune, or taken from the motor nameplate
0.00 to 3276.70 A
product
code
dependent
27.14
(induction
motor
only)
STATOR RES
This parameter contains the motor model per-
phase stator resistance as determined by
Autotune.
0.0000 to 250.0000
Ω
product
code
dependent
27.15
(induction
motor
only)
LEAKAGE INDUC
This parameter contains the motor model per-
phase leakage inductance as determined by
Autotune.
0.00 to 300.00mH
product
code
dependent
27.16
(induction
motor
only)
MUTUAL INDUC
This parameter contains the motor model per-
phase mutual inductance as determined by
Autotune.
0.00 to 3000.00mH
product
code
dependent
27.17
(induction
motor
only)
ROTOR TIME
CONST
This parameter contains the motor model
rotor time constant as determined by
Autotune.
10.00 to 3000.00ms
product
code
dependent