Programming
Page
D-192
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D
8
9
10
A
B
C
D
E
1
2
3
4
5
6
7
PREF
Name
Block
Type
Range
Default
ro\rw
Notes
21.28
USER FREQ 10
FLUXING
REAL
0.0 to 100.0 %
100.0 %
rw
21.29
USER VOLTAGE 10
FLUXING
REAL
0.0 to 100.0 %
100.0 %
rw
22.01
ENABLE
SLEW RATE LIMIT
BOOL
0 : FALSE
1 : TRUE
TRUE rw
22.02
ACCEL LIMIT
SLEW RATE LIMIT
REAL
1.0 to 1200.0 Hz/s
500.0 Hz/s
rw
22.03
DECEL LIMIT
SLEW RATE LIMIT
REAL
1.0 to 1200.0 Hz/s
500.0 Hz/s
rw
23.01
ENABLE
SLIP COMP
BOOL
0 : FALSE
1 : TRUE
FALSE rw
2
23.02
MOTORING LIMIT
SLIP COMP
REAL
0.0 to 600.0 RPM
150.0 RPM
rw
5
23.03
REGEN LIMIT
SLIP COMP
REAL
0.0 to 600.0 RPM
150.0 RPM
rw
5
25.01
ENABLE
STABILISATION
BOOL
0 : FALSE
1 : TRUE
TRUE rw
27.01
CONTROL MODE
MOTOR INDUCTION
ENUM
0 : VOLTS / Hz
1 : SENSORLESS VEC
2 : CLOSED-LOOP VEC
VOLTS / Hz
rw
2
27.02
POWER
MOTOR INDUCTION
REAL
0.00 to 3000.00 kW
30.00 kW
rw
3
27.03
BASE FREQUENCY
MOTOR INDUCTION
REAL
7.5 to 1000.0 Hz
50.0 Hz
rw
2,4
27.04
MOTOR VOLTAGE
MOTOR INDUCTION
REAL
0.0 to 690.0 V
400.0 V
rw
3,4
27.05
MOTOR CURRENT
MOTOR INDUCTION
REAL
0.00 to 3276.70 A
54.00 A
rw
2,3
27.06
MAG CURRENT
MOTOR INDUCTION
REAL
0.00 to 3276.70 A
16.20 A
rw
3
27.07
NAMEPLATE RPM
MOTOR INDUCTION
REAL
0.0 to 30000.0 RPM
1470.0 RPM
rw
3,4
27.08 MOTOR
CONNECTION
MOTOR INDUCTION
ENUM
0 : DELTA
1 : STAR
STAR rw
3,4
27.09
MOTOR POLES
MOTOR INDUCTION
ENUM
0 : 2 POLE
1 : 4 POLE
2 : 6 POLE
3 : 8 POLE
4 : 10 POLE
5 : 12 POLE
4 POLE
rw