Programming
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D
Page
D-63
8
9
10
A
B
C
D
E
1
2
3
4
5
6
7
Parameter Descriptions
INVERT
PREF: 153.05, 154.05
Default: FALSE
Range: FALSE / TRUE
This parameter inverts the active output state.
If set to FALSE the output is true when the variable is within the range, if set to TRUE the output is true when the variable is
outside the range.
DESTINATION
PREF: 153.06, 154.06
Default: 0
Range: See below
This parameter sets which output is driven by the block.
Enumerated Value
:
State
0 : NONE
Only the ACTIVE output will be driven.
1 : DIG OUT 1
DIGITAL OUTPUT 1 will be driven along with the ACTIVE output.
2 : DIG OUT 2
DIGITAL OUTPUT 2 will be driven along with the ACTIVE output.
3 : DIG OUT 3
DIGITAL OUTPUT 3 will be driven along with the ACTIVE output.
4 : DIG OUT 4
DIGITAL OUTPUT 4 will be driven along with the ACTIVE output.
5 : DIG OUT 5
DIGITAL OUTPUT 5 will be driven along with the ACTIVE output.
6 : DIG OUT 6
DIGITAL OUTPUT 6 will be driven along with the ACTIVE output.
DEFAULT
PREF: 153.07, 154.07
Default: FALSE
Range: FALSE / TRUE
This parameter sets the ACTIVE output state when the block is disable.
ACTIVE
PREF: 153.08, 154.08
Default: FALSE
Range: FALSE / TRUE
This is a diagnostic output indicating the current state of the block.