![Parker 890CS Скачать руководство пользователя страница 319](http://html2.mh-extra.com/html/parker/890cs/890cs_product-manual_3748717319.webp)
Programming
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D
Page
D-35
8
9
10
A
B
C
D
E
1
2
3
4
5
6
7
Parameter Descriptions
TORQUE FEEDBACK
PREF: 70.10
Default: —.xx %
Range: —.xx %
Shows the estimated motor torque, as a percentage of rated motor torque.
FIELD FEEDBACK
PREF: 70.11
Default: —.xx %
Range: —.xx %
A value of 100% indicates the motor is operating at rated magnetic flux (field).
MOTOR CURRENT %
PREF: 70.12
Default: —.xx %
Range: —.xx %
This diagnostic contains the level of rms line current being drawn from the Drive and is seen as a % of the MOTOR
CURRENT parameter setting in the MOTOR DATA function block.
MOTOR CURRENT A
PREF: 70.13
Default: —.xx A
Range: —.xx A
This diagnostic contains the level of rms line current in Amps being drawn from the Drive.
STACK RATING A
PREF: 70.19
Default: —.x A
Range: —.x A
This diagnostic indicates the stack rating in Amps. This reduces as a function of pwm switching frequency.
HEATSINK TEMP
PREF: 70.17
Default: —. C
Range: —. C
This diagnostic displays the power stack heatsink temperature in
°
Centigrade.
HEATSINK TEMP
PREF: 70.18
Default: —. %
Range: —. %
This diagnostic displays the power stack heatsink temperature as a percentage of the overtemperature trip level.