Associated Equipment
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D
Page
6-9
8
9
10
11
A
B
C
D
1
2
3
4
5
6
7
E
890CS Dynamic Braking Resistors - Europe
These resistor sets (complete with cover) are designed for stopping the system at rated power.
They are rated for 10 seconds in a 100 seconds duty cycle.
IMPORTANT
The continuous rating of the quoted resistor is not to be exceeded under repetitive loading
conditions.
Frame
Size
Drive
Amps
(A)
Drive
Rating
(kW)
Brake
Volts
(V)
Peak
Amps
(A)
Minimum
Ohms
(
Ω
)
Cressall
Part
Number
Dimensions
L x W x H
(mm)
Resistance
(
Ω
)
Rated
Amps
(A)
Rated
Power
(W)
208/230 Vac
B
32
7.5
390
20
19.5
HP1-24R
505 x 138 x 135.5
24
8
1500
B
54
15
390
40
9.8
HP1-12R
505 x 138 x 135.5
12
11
1500
D
108
30
390
75
5.2
HP1-5R6
505 x 138 x 135.5
5.6
16
1500
D
162
45
390
100
3.9
HP2-4R7
505 x 138 x 135.5
4.7
25
3000
380/415 Vac
B
32
15
770
20
38.5
HP1-47R
505 x 138 x 135.5
47
5.6
1500
B
54
30
770
40
19.3
HP1-24R
505 x 138 x 135.5
24
8
1500
D
108
60
770
75
10.3
HP2-12R
505 x 233 x 135.5
12
16
3000
D
162
90
770
100
7.7
HP3-8R2
505 x 327 x 135.5
8.2
23
4500
500 Vac
B
32
18
830
20
41.5
HP1-47R
505 x 138 x 135.5
47
5.6
1500
B
54
37
830
40
20.8
HP1-24R
505 x 138 x 135.5
24
8
1500
D
108
75
830
75
11.1
HP2-12R
505 x 233 x 135.5
12
16
3000
D
162
110
830
100
8.3
HP3-10R
505 x 327 x 135.5
10
21
4500