Technical Specifications
E-12
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames E & F
Electrical Ratings: 890CS Frame D, 500V
Output current must not be exceeded under steady state operating conditions.
FRAME D : 108A AC rms Input Current (nominal power 60kW)
Model Number
890CS-533108D (890CS/5/0108D)
Operating Voltage
208V to 500V ±10%
Nominal Operating Voltage
V
208/230
380/415
460
500
Input Current
A
108
Continuous RMS Output Current
A
135
Output Power
30kW/40HP
60kW
90HP
75kW
Power Loss
W
300
300
300
300
Output Overload
150% overload for 60 seconds
Dynamic Brake Current Rating
(Note 1)
A
75
75
75
75
Input Bridge I
2
t
A
2
s
108,000
Prospective Short Circuit Current
kA
100
FRAME D : 162A AC rms Input Current (nominal power 90kW)
Model Number
890CS-533162D (890CS/5/0162D)
Operating Voltage
208V to 500V ±10%
Nominal Operating Voltage
V
208/230
380/415
460
500
Input Current
A
162
Continuous RMS Output Current
A
200
Output Power
45kW/60HP
90kW
135HP
110kW
Power Loss
W
500
500
500
500
Output Overload
150% overload for 60 seconds
Dynamic Brake Current Rating
A
100
100
100
100
Input Bridge I
2
t
A
2
s
128,000
Prospective Short Circuit Current
kA
100
Note 1: Based on 33% duty cycle at a braking resistor appropriate for braking at 100% of drive rated power.