8-47
Operating the Drive
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames E & F
5% Choke
Drive
Frame
Size
Motor
Power
Input
Voltage
Choke
Inductance
Currents
(kW/Hp)
(V)
(
µ
H)
50Hz
1kHz 2.5kHz Sum
B
4/5
230
CO468342U004
1424
14.85
0.30
2.72
16
C
7.5/10
230
CO468342U011
839
25.20
0.50
4.61
26
D
18.5/25
230
CO468342U018
346
61.20
1.22
11.20
63
E
22/30
230
CO468342U030
294
72.00
1.44
13.18
74
F
45/60
230
CO468342U055
153
138.60
2.77
25.36
141
B
6/10
400
CO468326U006
2918
12.60
0.25
2.31
13
C
15/20
400
CO468326U018
1362
27.00
0.54
4.94
28
D
30/40
400
CO468326U037
693
53.10
1.06
9.72
54
E
45/60
400
CO468326U055
470
78.30
1.57
14.33
80
F
90/150
400
CO468326U110
227
162.00
3.24
29.65
165
G
180/300
400
CO468326U220
114
324.90
6.50
59.46
331
H
280/450
400
CO468326U315
79
468.00
9.36
85.64
476
J
315/500
400
CO468326U355
70
531.00 10.62
97.17
540