Operating the Drive
8-48
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames E & F
8
9
10
11
A
B
C
D
1
2
3
4
5
6
E
3% Choke
Drive
Frame
Size
Motor
Power
Input
Voltage
Choke
Inductance
Currents
(kW/Hp)
(V)
(
µ
H)
50Hz
1kHz 2.5kHz Sum
B
4/5
230
CO468341U004
854
14.95
0.39
0.00
15
C
7.5/10
230
CO468341U011
503
25.38
0.66
0.00
26
D
18.5/25
230
CO468341U018
208
61.63
1.59
0.00
62
E
22/30
230
CO468341U030
177
72.50
1.87
0.00
73
F
45/60
230
CO468341U055
92
139.57
3.60
0.00
140
B
6/10
400
CO468325U006
1750
12.69
0.33
0.00
13
C
15/20
400
CO468325U018
817
27.19
0.70
0.00
28
D
30/40
400
CO468325U037
416
53.47
1.38
0.00
54
E
45/60
400
CO468325U055
282
78.85
2.04
0.00
79
F
90/150
400
CO468325U110
137
163.13
4.21
0.00
164
G
180/300
400
CO468325U220
68
327.17
8.45
0.00
328
H
280/450
400
CO468325U315
48
471.28 12.17
0.00
472
J
315/500
400
CO468325U355
42
534.72 13.81
0.00
535
Lower values for THD of current can be achieved by adding extra line impedance.