D-54
Programming
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames E & F
Parameter Descriptions
FIXED BOOST
PREF: 21.03
Default: 0.00 %
Range: 0.00 to 25.00 %
This parameter allows for no-load stator resistance voltage drop compensation. This correctly fluxes the motor (under no-load
conditions) at low output frequencies, thereby increasing available motor torque. Fixed boost can be set in addition to auto
boost and acceleration boost.
BASE FREQUENCY
0
100%
V
f
BOOST = 10%
AUTO BOOST
PREF: 21.04
Default: 0.00 %
Range: 0.00 to 25.00 %
This parameter allows for load dependent stator resistance voltage drop compensation. This correctly fluxes the motor (under
load conditions) at low output frequencies, thereby increasing available motor torque. Auto boost can be set in addition to fixed
boost.
The value of the AUTO BOOST parameter determines level of additional volts supplied to the motor for 100% load.
Setting the value of auto boost too high can cause the Drive to enter current limit. If this occurs, the Drive will be unable to
ramp up in speed. Reducing the value of auto boost will eliminate this problem.
ACCELRTN BOOST
PREF: 21.08
Default:0.00 %
Range: 0.00 to 25.00 %
This parameter provides an additional amount of fixed boost when the drive is accelerating. This can help when starting
heavy/high stiction loads.