890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames E & F
DIGITAL I/O
Name
Range
Description
X16
01
DOUT4A
open/closed
Normally-open relay contacts, A & B.
02
DOUT4B
open/closed
Default function DOUT4 closed = healthy
03
DOUT5A
open/closed
Normally-open relay contacts, A & B.
04
DOUT5B
open/closed
Default function DOUT5 closed = running
05
DOUT6A
open/closed
Normally-open relay contacts, A & B.
06
DOUT6B
open/closed
No default function.
07
NC
Not Connected - this terminal is unused
08
MTR THRM A
Motor thermistor connection,
or link to MTR THRM B
09
MTR THRM B
Motor thermistor connection,
or link to MTR THRM A
All digital inputs/outputs are configurable using the DSE 890 (Drive System Explorer) Configuration Tool
supplied on disk. The table shows the factory defaults. The digital inputs require 24V DC which is supplied
at terminal X14/03. For further information refer to the DSE 890 Configuration Tool.
Relay outputs are volt-free, normally open contacts. Rated to 240V 3A resistive load. Alternatively they
may be used down to 1mA, 12V levels.