15-14
Parameter Reference
AC10 Inverter
Function
Code
Function
Definition
Setting Range
Mfr’s Value Change
F706
Inverter Overloading coefficient
%
120
~
190
150
╳
F707
Motor Overloading coefficient
%
20
~
100
100
╳
F708
Trip 1 Type (Newest)
Setting range:
2: Over current (OC)
3: Over voltage (OE)
4: Input phase loss (PF1)
5: Inverter overload (OL1)
6: Under voltage (LU)
7: Overheat (OH)
8: Motor overload (OL2)
11: External malfunction (ESP)
12: Current fault before running (Err3)
13. Studying parameters without
motor (Err2)
15: Current sampling fault (Err4)
16: Over current 1 (OC1)
17: Output phase loss (PF0)
18: Aerr analog disconnected
23: Err5 PID parameters are set wrong
45: Communication Timeout (CE)
46: Flycatching fault (FL)
49: Watchdog fault (Err6)
67: Overcurrent (OC2)
△
F709
Trip 2 Type
△
F710
Trip 3 Type
△
F711
Trip 1 Fault Frequency
△
F712
Trip 1 Fault Current
△
F713
Trip 1 Fault DC Bus Voltage
△
F714
Trip 2 Fault Frequency
△
F715
Trip 2 Fault Current
△
F716
Trip 2 Fault DC Bus Voltage
△
F717
Trip 3 Fault Frequency
△
F718
Trip 3 Fault Current
△
F719
Trip 3 Fault DC Bus Voltage
△
F720
Number of Overcurrent Faults
△
F721
Number of Overvoltage Protection Faults
△
F722
Number of Overload Protection Fault
△
F723
Number of Overload Protection Fault
△
F724
Input Phase Loss
0: Disabled
1: Enabled
1
○
╳
F725
Reserved
F726
Overheat
0: Disabled
1: Enabled
1
○
╳
F727
Output Phase Loss
0: Disabled
1: Enabled
0
○
F728
Input Phase Loss Filtering Constant
0.1
~
60.0
0.5
√
F730
Overheat Protection Filtering Constant
0.1
~
60.0
5.0
√
Содержание 10G-46-0600-BF
Страница 2: ......
Страница 18: ...Installation 3 3 AC10 Inverter 3 3 Inverters Installed in a Control Cabinet...
Страница 26: ...Installation Connection 7 2 AC10 Inverter Metal Cover Layout Frames 6 11...
Страница 112: ...The Default Applications 13 2 AC10 Inverter 13 1Application 1 Basic Speed Control F228 1...
Страница 114: ...The Default Applications 13 4 AC10 Inverter 13 2 Application 2 Auto Manual Control F228 2...
Страница 116: ...The Default Applications 13 6 AC10 Inverter 13 3 Application 3 Preset Speeds F228 3...
Страница 118: ...The Default Applications 13 8 AC10 Inverter 13 4 Application 4 Raise Lower Secondary F228 4...
Страница 120: ...The Default Applications 13 10 AC10 Inverter 13 5Application 5 PID F228 5...