13-3
The Default Applications
AC10 Inverter
This Application is ideal for general purpose applications. The set-point is the sum of the two
analogue inputs AI1 and AI2, providing Speed Set-point + Speed Secondary capability.
Function setting
Setting value
F228 Macro selection
1: Basic speed control
F106 Control mode
2: VF control
F203 Main frequency source X
1: AI1
F204 Accessorial frequency source Y
2: AI2
F207 Frequency source selecting
1: X+Y
F316 DI1 terminal function setting
1: Running terminal
F317 DI2 terminal function setting
58: Direction
F318 DI3 terminal function setting
52: Jogging terminal (no direction)
F319 DI4 terminal function setting
2: Stop terminal
F320 DI5 terminal function setting
8: Free stop terminal
F431 AO1 analog output signal selecting
0: Running frequency
Coast stop
1
2
3
5
6
4
7
8
9
10
11
12
13
14
15
16
17
18
TA
TB
TC
1
DO
24
V
CM
DI1
DI2
DI3
DI4
DI5
10
V
1
AI
2
AI
GND
1
AO
A
B
REF
Stop
Jog
Direction
Run
Speed trim
not used
not used
Analog output
F431=0 , running
frequency is output
.
GND
Speed trim
AI 2 input 4-20 mA
Speed setpointAI 1 input 0-10V
10V
Coast stop
Stop
Jog
The jogging direction is
controlled by DI2.
Direction
When the function is valid,
inverter runs reverse
Run
CM
24V
not used
Relay output
Содержание 10G-46-0600-BF
Страница 2: ......
Страница 18: ...Installation 3 3 AC10 Inverter 3 3 Inverters Installed in a Control Cabinet...
Страница 26: ...Installation Connection 7 2 AC10 Inverter Metal Cover Layout Frames 6 11...
Страница 112: ...The Default Applications 13 2 AC10 Inverter 13 1Application 1 Basic Speed Control F228 1...
Страница 114: ...The Default Applications 13 4 AC10 Inverter 13 2 Application 2 Auto Manual Control F228 2...
Страница 116: ...The Default Applications 13 6 AC10 Inverter 13 3 Application 3 Preset Speeds F228 3...
Страница 118: ...The Default Applications 13 8 AC10 Inverter 13 4 Application 4 Raise Lower Secondary F228 4...
Страница 120: ...The Default Applications 13 10 AC10 Inverter 13 5Application 5 PID F228 5...