9-6
AC10 Inverter
Whatever the value of F131 is set to, corresponding target frequency will flash under stopped
status.
Target rotary speed is an integral number. If it exceeds 9999, add a decimal point to it.
Keypad Displays
Current
A*.*
DC Bus Voltage U***
Output Voltage
u***
Temperature
H***
Linear Speed
L***
PID Reference
O*.*
PID Feedback
B*.*
Output power
*.*
Output torque
*.*
If it exceeds 999, add a decimal point to it.
If it exceeds 9999, add two decimal points to it, and the like.
F132 Display items of stop
Setting range:
0: Frequency/function-code
1: Keypad jogging
2: Target rotary speed
4: DC Bus Voltage
8: PID feedback value
16: Temperature
32: Reserved
64: PID given value
128: Reserved
256: Reserved
512: Setting torque
Mfr’s value:
0+2+4
=
6
F133 Drive ratio of driven system
Setting range: 0.10
~
200.0
Mfr’s value:
1.00
F134 Transmission-wheel radius
0.001
~
1.000 (m)
Mfr’s value:
0.001
Calculation of rotary speed and linear speed:
For example, If inverter’s max frequency F111=50.00Hz, numbers of motor poles F804=4,
drive ratio F133
=
1.00, transmission-shaft radius R=0.05m, then
Transmission shaft perimeter: 2πR =2×3.14×0.05=0.314 (meter)
Transmission shaft rotary speed: 60× operation frequency/ (numbers of poles pairs × drive
ratio) =60×50/ (2×1.00) =1500rpm
Maximum linear speed: rotary speed × perimeter=1500×0.314=471(meters/second)
F136 Slip compensation
Setting range: 0
~
10
Mfr’s value: 0
Under V/HZ controlling, rotary speed of motor rotor will decrease as load increases. Be
assured that rotor rotate speed is near to synchronization rotary speed while motor with rated
load, slip compensation should be adopted according to the setting value of frequency
compensation.
Note: During the process of Flycatching, slip compensation function is invalid. After
Flycatching is finished, this function is valid.
F137 Modes of torque
compensation
Setting range:
0: Linear compensation;
1: Square compensation;
2: User-defined multipoint compensation
3: Auto torque compensation
Mfr’s value: 3
F138 Linear compensation
Setting range: 1
~
20
Mfr’s value:
subject to
inverter model
F139 Square compensation
Setting range:
1: 1.5
2: 1.8
3: 1.9
4: 2.0
Mfr’s value: 1
Содержание 10G-46-0600-BF
Страница 2: ......
Страница 18: ...Installation 3 3 AC10 Inverter 3 3 Inverters Installed in a Control Cabinet...
Страница 26: ...Installation Connection 7 2 AC10 Inverter Metal Cover Layout Frames 6 11...
Страница 112: ...The Default Applications 13 2 AC10 Inverter 13 1Application 1 Basic Speed Control F228 1...
Страница 114: ...The Default Applications 13 4 AC10 Inverter 13 2 Application 2 Auto Manual Control F228 2...
Страница 116: ...The Default Applications 13 6 AC10 Inverter 13 3 Application 3 Preset Speeds F228 3...
Страница 118: ...The Default Applications 13 8 AC10 Inverter 13 4 Application 4 Raise Lower Secondary F228 4...
Страница 120: ...The Default Applications 13 10 AC10 Inverter 13 5Application 5 PID F228 5...