The Default Applications
AC10 Inverter
This Application mimics the operation of a motorised potentiometer. Digital inputs allow the set-point to be increased
and decreased between limits. The Application is sometimes referred to as motorised Potentiometer.
Function setting
Setting value
F228 Macro selection
4: Raise/Lower
F106 Control mode
2: VF control
F112 Min Frequency
Min frequency is 0.00Hz.
F113 Target frequency
Target frequency is 0.00Hz.
F224 when target frequency is lower than Min
frequency
1: When target frequency is lower than Min
frequency, inverter will run at Min frequency.
F203 Main frequency source X
0: Digital setting memory
F208 Terminal two-line/three-line operation selecting
1: Two-line operation mode 1
F316 DI1 terminal function setting
15: FWD terminal
F317 DI2 terminal function setting
13: UP frequency increasing
F318 DI3 terminal function setting
14: DOWN frequency decreasing
F319 DI4 terminal function setting
54: Frequency reset
F320 DI5 terminal function setting
8: Free stop
F431 AO1 analog output signal selecting
0: Running frequency
Coast stop
1
2
3
5
6
4
7
8
9
10
11
12
13
14
15
16
17
18
TA
TB
TC
1
DO
24
V
CM
DI1
DI2
DI3
DI4
DI5
10
V
1
AI
2
AI
GND
1
AO
A
B
Run forward
not used
not used
Analog output F431=0 , running frequency is output.
GND
10V
Coast stop
Reset
Run forward
CM
24V
not used
Relay output
F300=1 , inverter outputs fault signal
.
Lower input
Raise input
Reset
Lower input
Raise input
not used
not used
Содержание 10G-46-0600-BF
Страница 2: ......
Страница 18: ...Installation 3 3 AC10 Inverter 3 3 Inverters Installed in a Control Cabinet...
Страница 26: ...Installation Connection 7 2 AC10 Inverter Metal Cover Layout Frames 6 11...
Страница 112: ...The Default Applications 13 2 AC10 Inverter 13 1Application 1 Basic Speed Control F228 1...
Страница 114: ...The Default Applications 13 4 AC10 Inverter 13 2 Application 2 Auto Manual Control F228 2...
Страница 116: ...The Default Applications 13 6 AC10 Inverter 13 3 Application 3 Preset Speeds F228 3...
Страница 118: ...The Default Applications 13 8 AC10 Inverter 13 4 Application 4 Raise Lower Secondary F228 4...
Страница 120: ...The Default Applications 13 10 AC10 Inverter 13 5Application 5 PID F228 5...