Parameter Reference
15-5
AC10 Inverter
Function
Code
Function Definition
Setting Range
Mfr’s Value Change
F208
Terminal operation mode
0: No function
1: Two-line operation mode 1
2: Two-line operation mode 2
3: Three-line operation mode 1
4: Three-line operation mode 2
5: Start/stop controlled by direction
pulse
0
╳
F209
Motor stopping mode
0: stop by deceleration time
1: free stop (coast stop)
0
╳
F210
Frequency display accuracy
0.01
~
2.00
0.01
√
F211
Speed of digital control
0.01
~
100.00Hz/S
5.00
√
F212
Direction memory
0: Disabled
1: Enabled
0
√
F213
Auto-starting after repowered on
0: Disabled
1: Enabled
0
√
F214
Auto-starting after reset
0: Disabled
1: Enabled
0
√
F215
Auto-starting delay time
0.1
~
3000.0
60.0
√
F216
Auto-start restart attempts
0
~
5
0
√
F217
Fault reset delay
0.0
~
10.0
3.0
√
F218
Reserved
F219
Write EEPROM by Modbus
0: Disabled
1: Enabled
1
√
F220
Frequency memory after power-down
0: Disabled
1: Enabled
0
√
F221-
F223
Reserved
F224
When target frequency is lower than Min
frequency
0: Stop
1: run at min frequency
1
√
F225-
F227
Reserved
F228
Application selection
0: None
1: Basic speed control
2: Auto/manual control
3: Stage speed control
4: Terminal control
5: PID control
0
No Macro
selected
F229~
F230
Reserved
Содержание 10G-46-0600-BF
Страница 2: ......
Страница 18: ...Installation 3 3 AC10 Inverter 3 3 Inverters Installed in a Control Cabinet...
Страница 26: ...Installation Connection 7 2 AC10 Inverter Metal Cover Layout Frames 6 11...
Страница 112: ...The Default Applications 13 2 AC10 Inverter 13 1Application 1 Basic Speed Control F228 1...
Страница 114: ...The Default Applications 13 4 AC10 Inverter 13 2 Application 2 Auto Manual Control F228 2...
Страница 116: ...The Default Applications 13 6 AC10 Inverter 13 3 Application 3 Preset Speeds F228 3...
Страница 118: ...The Default Applications 13 8 AC10 Inverter 13 4 Application 4 Raise Lower Secondary F228 4...
Страница 120: ...The Default Applications 13 10 AC10 Inverter 13 5Application 5 PID F228 5...